AWG vs mm²: which metric size replaces which AWG, and why the ampacity does not convert
AWG sizes convert to mm² exactly: 14 AWG is 2.08 mm², 12 AWG is 3.31 mm², 10 AWG is 5.26 mm², 8 AWG is 8.37 mm² and 6 AWG is 13.3 mm². No AWG size equals a standard metric size, so 2.5 mm² is neither 14 AWG nor 12 AWG: it sits between them. When one replaces the other, round up to the next size: 4 mm² in place of 12 AWG, or 12 AWG in place of 2.5 mm². Then check the replacement's ampacity in the standard that governs the installation, NEC Table 310.16 (2023 edition) in the United States or IEC 60364-5-52 in most other countries, because the two allow different currents on similar copper.
Converting the number is arithmetic. The mistake is treating the result as an equivalent: a 2.5 mm² cable (also written mm2 or sq mm) is not "metric 12 gauge", and 14 AWG is not "American 2.5 mm²". Below are both tables, how to substitute, and why the ampacity does not convert with the area.
AWG to mm²: the next metric size up for each gauge
| AWG | Area | Next metric size up | Next metric size down |
|---|---|---|---|
| 14 AWG | 2.08 mm² | 2.5 mm² | 1.5 mm² |
| 12 AWG | 3.31 mm² | 4 mm² | 2.5 mm² |
| 10 AWG | 5.26 mm² | 6 mm² | 4 mm² |
| 8 AWG | 8.37 mm² | 10 mm² | 6 mm² |
| 6 AWG | 13.3 mm² | 16 mm² | 10 mm² |
| 4 AWG | 21.2 mm² | 25 mm² | 16 mm² |
| 3 AWG | 26.7 mm² | 35 mm² | 25 mm² |
| 2 AWG | 33.6 mm² | 35 mm² | 25 mm² |
| 1 AWG | 42.4 mm² | 50 mm² | 35 mm² |
| 1/0 AWG | 53.5 mm² | 70 mm² | 50 mm² |
| 2/0 AWG | 67.4 mm² | 70 mm² | 50 mm² |
| 3/0 AWG | 85.0 mm² | 95 mm² | 70 mm² |
| 4/0 AWG | 107 mm² | 120 mm² | 95 mm² |
The full chart from 18 AWG to 500 kcmil, with circular mils, is on the AWG to mm² converter page.
mm² to AWG: which AWG replaces 1.5, 2.5, 4, 6 and 10 mm²?
For each standard metric size, this is the smallest AWG size with at least as much copper:
| Metric size | Next AWG size up | Area of that AWG size |
|---|---|---|
| 1.5 mm² | 14 AWG | 2.08 mm² |
| 2.5 mm² | 12 AWG | 3.31 mm² |
| 4 mm² | 10 AWG | 5.26 mm² |
| 6 mm² | 8 AWG | 8.37 mm² |
| 10 mm² | 6 AWG | 13.3 mm² |
| 16 mm² | 4 AWG | 21.2 mm² |
| 25 mm² | 3 AWG | 26.7 mm² |
| 35 mm² | 1 AWG | 42.4 mm² |
| 50 mm² | 1/0 AWG | 53.5 mm² |
| 70 mm² | 3/0 AWG | 85.0 mm² |
| 95 mm² | 4/0 AWG | 107 mm² |
| 120 mm² | 250 kcmil | 127 mm² |
Can you use metric cable in place of AWG, or AWG in place of mm²?
- The installation's standard governs, not where the equipment was made. A European machine installed in the United States is wired to the NEC.
- Convert and round up, never down.
- Check that size in the local ampacity table for the breaker and the way it is installed, and go up if it fails. For the NEC side, the wire size calculator does this check for copper or aluminum; the full method is in how to size wire by the NEC.
- Check the terminals. For a terminal range, round down: a lug marked "max 16 mm²" takes 6 AWG (13.3 mm²), not 4 AWG (21.2 mm²). Finely stranded metric flexible cable needs a terminal identified for that stranding, or a ferrule or listed connector (110.14).
- The breaker comes from the nameplate, not from the cable.
Example 1: an imported machine's manual asks for a 3 × 6 mm² supply on 32 A, and it is being installed in the US. The next AWG size up is 8 AWG copper (8.37 mm²), 40 A in the 60 °C column. Do not round the protection up past the manual. If 32 A is the maximum protective device the maker allows, use a 30 A breaker where the machine's current permits it, or a listed 32 A breaker or fuse (240.6(A) permits non-standard ratings). If 32 A is the load current, the breaker follows the NEC rules for that load: 35 A if the load is not continuous, 40 A if it is, and never above the nameplate maximum (110.3(B)).
Example 2: a US appliance asks for 10 AWG copper on a 30 A circuit, and it is being installed in an IEC country. The instructions set a minimum of 5.26 mm², so the cable is 6 mm², not 4 mm². 30 A is not an IEC breaker rating: use 25 A if the appliance's current allows it, or 32 A only if the manufacturer permits protection above 30 A. 6 mm² carries at least 32 A for installation methods A1 to C at 30 °C (exactly 32 A for method A2), so grouping or a hotter room lowers that figure.
AWG vs mm² ampacity: why the same copper carries different amps under NEC and IEC
An AWG size cannot simply be converted to mm² because the current a conductor may carry is set by the installation standard, not by the copper area. For similar areas the two standards allow these currents (IEC 60364-5-52 for PVC-insulated copper, two loaded conductors, 30 °C, from method A2 in an insulated wall to method C clipped to a wall; NEC Table 310.16 with the breaker limits of 240.4(D)):
| Conductor | Area | Ampacity in its own standard |
|---|---|---|
| 1.5 mm² | 1.5 mm² | 14 A to 19.5 A, by installation method (IEC) |
| 14 AWG | 2.08 mm² | 15 A at 60 °C, 20 A at 75 °C; breaker limited to 15 A (NEC) |
| 2.5 mm² | 2.5 mm² | 18.5 A to 27 A (IEC) |
| 12 AWG | 3.31 mm² | 20 A at 60 °C, 25 A at 75 °C; breaker limited to 20 A (NEC) |
| 4 mm² | 4 mm² | 25 A to 36 A (IEC) |
| 10 AWG | 5.26 mm² | 30 A at 60 °C, 35 A at 75 °C; breaker limited to 30 A (NEC) |
| 6 mm² | 6 mm² | 32 A to 46 A (IEC) |
| 8 AWG | 8.37 mm² | 40 A at 60 °C, 50 A at 75 °C (NEC) |
The clearest case is the smallest one. A 1.5 mm² cable clipped to a wall can go on a 16 A breaker in an IEC installation. The NEC holds 14 AWG, which has 39% more copper, to a 15 A breaker. Neither is wrong; the standards assume different things:
- Installation method. IEC ampacity depends on how the cable is installed, with separate columns for methods A1 to E. The NEC uses one main table and then adjusts it.
- Temperature ratings. IEC tables are built for 70 °C PVC and 90 °C XLPE. The NEC has 60, 75 and 90 °C columns and limits the result to the termination rating (110.14(C)).
- Small-conductor limits. NEC 240.4(D) caps the breaker on 14, 12 and 10 AWG. IEC 60364 has no matching rule.
- Breaker ratings. 15, 20 and 30 A in North American practice; 6, 10, 13, 16, 20, 25 and 32 A in IEC practice.
- System voltage. The same power at 230 V is about half the current it is at 120 V, and the same loss in volts is half the percentage.
Aluminum needs about 1.6 times the area of copper for the same resistance, usually two AWG sizes up: in NEC Table 310.16 at 75 °C, 8 AWG copper and 6 AWG aluminum are both 50 A.
What is the formula to convert AWG to mm²?
AWG (American Wire Gauge) is a geometric series of diameters: a larger number is a smaller wire, and every six gauge numbers double the diameter, so 6 AWG has four times the copper of 12 AWG. Above 4/0 the sizes are given in kcmil, and 1 kcmil is 0.5067 mm².
diameter, mm = 0.127 × 92^((36 − AWG) ÷ 39)
area, mm² = 0.012668 × 92^((36 − AWG) ÷ 19.5)
12 AWG: 0.012668 × 92^(24 ÷ 19.5) = 3.31 mm²
For 1/0, 2/0, 3/0 and 4/0 use 0, −1, −2 and −3 as the AWG number.
Metric sizes are nominal. IEC 60228 defines each one by its maximum resistance, not by a measured area: a 2.5 mm² copper conductor may have no more than 7.41 Ω per km at 20 °C, and a 1.5 mm² one no more than 12.1 Ω per km.
In the browser: the free AWG to mm² converter and the NEC ampacity chart.
AWG and mm² questions
Is 2.5 mm² 12 AWG or 14 AWG?
2.5 mm² is neither: it sits between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²). It has 20% more copper than 14 AWG and 24% less than 12 AWG, so it cannot replace 12 AWG where 12 AWG is required.
What is 12 AWG in mm²?
12 AWG is 3.31 mm². It sits between the metric sizes 2.5 mm² and 4 mm², so the metric replacement is 4 mm², the next size up.
What is 14 AWG in mm²?
14 AWG is 2.08 mm². It sits between 1.5 mm² and 2.5 mm², so the metric replacement is 2.5 mm². 14 AWG has 39% more copper than 1.5 mm² and 17% less than 2.5 mm².
What is 4 mm² in AWG?
4 mm² falls between 12 AWG (3.31 mm²) and 10 AWG (5.26 mm²). The AWG replacement is 10 AWG; 12 AWG has 17% less copper than 4 mm².
Can I use 2.5 mm² wire on a 20 amp breaker?
Not under the NEC: a 20 A breaker needs at least 12 AWG copper (3.31 mm²) by 240.4(D). Under IEC 60364, 2.5 mm² copper can be protected at 20 A only where its installation method gives at least 20 A, such as clipped to a wall (method C, 27 A) or in conduit on a wall (method B1, 24 A); in an insulated wall (methods A1 and A2, 19.5 A and 18.5 A) it cannot.
How do I convert kcmil to mm²?
To convert kcmil to mm², multiply by 0.5067. 250 kcmil is 127 mm² and 500 kcmil is 253 mm².
Is 2.5 mm² the diameter of the wire?
No, mm² is the cross-sectional area of the conductor, not its diameter. A solid 2.5 mm² conductor is about 1.78 mm across, and a solid 12 AWG conductor (3.31 mm²) is about 2.05 mm across.
Can I use the ampacity of the AWG size for the metric cable I substituted?
No. Use the ampacity table of the standard that applies where the cable is installed. NEC Table 310.16 and IEC 60364-5-52 give different currents for similar areas because they assume different installation methods, temperatures and breaker rules.
More guides
- 8 AWG or 6 AWG for 50 amps?
- How to calculate box fill
- How to calculate conduit fill
- Continuous load: the 125% and 80% rules
- How to size wire step by step
- Voltage drop: 3% or 5%?
Written by Andrii Zhukovskyi, a software developer and the maker of Electrician Calc. He is not a licensed electrician. The numbers follow NFPA 70, National Electrical Code, 2023 edition, and are the values the app uses (methodology and sources); the code text is not reproduced. Under the 2017 NEC, Table 310.16 is Table 310.15(B)(16), 310.15(C)(1) is 310.15(B)(3)(a) and 310.12 is 310.15(B)(7). Found a mistake? Write to [email protected]. Reference only: the edition and amendments adopted where you work, the equipment listing and the manufacturer's instructions govern. NEC® and NFPA 70® are registered trademarks of the National Fire Protection Association; this site is not affiliated with or endorsed by NFPA.