How to size wire by the NEC, step by step: ampacity table, temperature, derating and voltage drop

In short

To size a wire by the NEC (2023 edition), work in this order: find the load and multiply it by 1.25 if it is continuous, pick the breaker, choose the termination column of Table 310.16 (60 °C or 75 °C), read the smallest size that carries the current, apply the ambient temperature and derating factors to the insulation's own column, check the 240.4(D) limits for 14, 12 and 10 AWG, check voltage drop, then size the ground from Table 250.122. The wire has to pass every check, so the largest size any step asks for is the answer. Example: a 24 A continuous load 180 ft away at 240 V needs 8 AWG copper on a 30 A breaker, because voltage drop, not ampacity, sets the size.

A wire size chart gives one number for one set of conditions. On a real job the conditions change: the conduit is full, the attic is hot, the run is long. Below is the method in the order the code applies it, one example from start to finish, and the tables you need.

How to size wire in 8 steps

Wire sizing by the 2023 NEC, in order
StepWhat you doNEC
1. LoadFind the current the circuit carries. Multiply a continuous load (3 hours or more) by 1.25.210.19(A)(1), 215.2(A)(1)
2. BreakerTake the next standard rating at or above that design current.240.6(A), 210.20(A)
3. Termination column60 °C for NM-B cable (Romex) and for equipment of 100 A or less that is not marked; 75 °C when the breaker and the equipment are marked for it.110.14(C), 334.80
4. AmpacityPick the smallest size whose ampacity in that column is at least the design current.Table 310.16
5. Conditions of useApply the ambient and derating factors to the insulation's own column. The result must still carry the load, and the breaker must still protect it: it may be above the derated ampacity only when it is the next standard size up. Otherwise go up a wire size.310.15(B), 310.15(C)(1), 240.4(B)
6. Small conductorsBreaker no larger than 15 A on 14 AWG, 20 A on 12 AWG, 30 A on 10 AWG copper.240.4(D)
7. Voltage dropUpsize if the drop is over 3% on the branch circuit.210.19, informational note
8. GroundSize the equipment grounding conductor (ground wire) from the breaker rating, and increase it if step 7 increased the wire.Table 250.122, 250.122(B)

Motors and air-conditioning equipment are sized by their own rules: motors by 430.22 and 430.52, air conditioners and heat pumps from the nameplate minimum circuit ampacity and maximum breaker (Article 440).

Wire sizing example: a 24 amp continuous load, six conductors in conduit, 104 °F

A 240 V load draws 24 A for hours at a time, so it is a continuous load. The wire is copper THHN in EMT with 75 °C terminations at both ends. The conduit holds six current-carrying conductors and crosses a space that reaches 40 °C (104 °F). The run is 180 ft one way.

  1. Load: continuous, so 24 × 1.25 = 30 A.
  2. Breaker: 30 A.
  3. Column: 75 °C.
  4. Ampacity: 12 AWG is 25 A, too small. 10 AWG is 35 A, enough for 30 A.
  5. Conditions: 10 AWG THHN is 40 A in the 90 °C column. 40 × 0.91 (ambient) × 0.80 (six conductors) = 29.1 A. That is more than the 24 A load, and 30 A is the next standard breaker above 29.1 A, which 240.4(B) permits.
  6. Small conductors: 10 AWG can go on a breaker up to 30 A. Pass.
  7. Voltage drop: 2 × 12.9 × 24 × 180 ÷ 10,380 = 10.7 V, or 4.5% of 240 V. Over the 3% voltage drop recommendation. 8 AWG gives 6.8 V, or 2.8%.
  8. Ground: Table 250.122 gives 10 AWG copper for a 30 A breaker. The circuit conductors went up from 10 to 8 AWG for voltage drop, so the ground goes up in the same proportion, to 8 AWG.

Result: 8 AWG copper THHN on a 30 A breaker with an 8 AWG ground. Ampacity alone allows 10 AWG; the 180 ft run sets the size. The wire size calculator runs the same checks if you want to try your own numbers.

Which column of Table 310.16 do you use: 60, 75 or 90 °C?

The column is set by the weakest point of the circuit, which is usually a termination, not the wire. NEC 110.14(C) uses the 60 °C column for circuits of 100 A or less (14 to 1 AWG) unless the equipment is listed and marked for 75 °C. Most current breakers and panels carry a "60/75 °C" marking, so THHN or THWN in conduit normally uses the 75 °C column. NM-B cable always uses the 60 °C column, whatever the breaker says (334.80).

Copper ampacity, NEC Table 310.16: up to three current-carrying conductors, 30 °C (86 °F) ambient
Copper size60 °C75 °C90 °C
14 AWG15 A20 A25 A
12 AWG20 A25 A30 A
10 AWG30 A35 A40 A
8 AWG40 A50 A55 A
6 AWG55 A65 A75 A
4 AWG70 A85 A95 A
3 AWG85 A100 A115 A
2 AWG95 A115 A130 A
1 AWG110 A130 A145 A
1/0 AWG125 A150 A170 A

You cannot use the 90 °C column at the breaker: breaker and device terminals are rated 60 or 75 °C. The 90 °C column is where derating starts for THHN and other 90 °C wire (step 5). The NEC Table 310.16 ampacity chart has every size, with aluminum; for a quick size by breaker, see what size wire for a 30, 40 or 50 amp breaker.

How do you derate wire for heat and for more than three conductors in a conduit?

Table 310.16 assumes 30 °C (86 °F) around the wire and no more than three current-carrying conductors together. Hotter surroundings and fuller raceways lower the ampacity, and the two factors are multiplied together.

Ambient temperature correction factors, based on 30 °C (NEC 310.15(B))
Ambient temperature60 °C wire75 °C wire90 °C wire
31–35 °C (87–95 °F)0.910.940.96
36–40 °C (96–104 °F)0.820.880.91
41–45 °C (105–113 °F)0.710.820.87
46–50 °C (114–122 °F)0.580.750.82
51–55 °C (123–131 °F)0.410.670.76
Adjustment (derating) factors for more than three current-carrying conductors (NEC Table 310.15(C)(1))
Current-carrying conductors in the raceway or cableFactor
1–31.00
4–60.80
7–90.70
10–200.50
21–300.45
31–400.40
41 and more0.35

Every hot conductor counts as current-carrying. A neutral counts when it is the return of a 2-wire circuit; the shared neutral of a 120/240 V multiwire circuit that carries only the imbalance does not. The neutral of a 3-wire circuit taken from a 208Y/120 V system does count, and so does a neutral that serves mostly nonlinear loads (310.15(E)). Grounds never count (310.15(F)). Counting conductors in a full conduit is worked through in how to calculate conduit fill.

NM-B gets the same treatment: more than two NM cables bundled together, or run without spacing through the same framing hole that is sealed with insulation, caulk or foam, are derated by the same table (334.80).

Two rules keep derating from oversizing the wire. First, the factors apply to the ampacity of the insulation, so THHN starts from the 90 °C column. Second, the derated ampacity is compared with the load itself, not with 125% of it. The 125% for a continuous load is checked separately at the termination column, without the factors. NEC 210.19(A) makes these two separate checks, and the larger wire wins.

Common wire sizing mistakes

  • Reading the 90 °C column for the breaker. 10 AWG THHN is not a 40 A wire at a 60 or 75 °C terminal.
  • Stacking 125% on top of derating. They are two separate checks. Multiplying both together oversizes the wire.
  • Sizing NM-B from the 75 °C column. A 50 A circuit needs 6 AWG in NM-B, not 8 AWG (334.80, 60 °C column).
  • Derating without checking the breaker. 12 AWG THHN with ten current-carrying conductors is 15 A, so it cannot stay on a 20 A breaker even if the load is only 14 A.
  • Skipping voltage drop, or running it on the breaker rating when the real load is much smaller.
  • Leaving the ground at table size after the circuit conductors were increased.

These are also the settings that make two calculators disagree: see why calculators give 8 AWG or 6 AWG for 50 amps. For the 125% step on its own, see continuous load and the 125% rule.

Wire sizing questions

Do you apply the 125% and the derating factors at the same time?

No. NEC 210.19(A) makes two separate checks: the wire must carry 125% of the continuous load in the termination column without ambient or derating factors, and it must carry 100% of the load after those factors are applied. The larger of the two sizes is the answer; multiplying 1.25 and the derating factors together oversizes the wire.

Do I derate from the 75 °C or the 90 °C column?

Derate from the column that matches the insulation. THHN, THWN-2 and XHHW-2 are 90 °C insulations, so their ambient and derating factors apply to the 90 °C ampacity in NEC Table 310.16. The result still may not exceed the ampacity in the termination column.

Is NM-B (Romex) sized from the 60 °C or the 90 °C column?

NM-B cable (Romex) is sized from the 60 °C column of NEC Table 310.16 (334.80), even though its conductors are rated 90 °C. The 90 °C ampacity may be used only as the starting point for derating, and the final result may not exceed the 60 °C value.

Can I round up to the next breaker size?

Yes, within limits. When a conductor's ampacity does not match a standard breaker rating, NEC 240.4(B) allows the next standard size up, as long as the breaker is 800 A or less and the circuit does not supply multiple receptacles for cord-and-plug loads. The 240.4(D) limits on 14, 12 and 10 AWG still apply.

Does the neutral count as a current-carrying conductor?

The neutral of a 2-wire circuit counts. The neutral of a 120/240 V multiwire circuit that carries only the unbalanced current does not; the neutral of a 3-wire circuit from a 208Y/120 V system and a neutral serving mostly nonlinear loads do (NEC 310.15(E)). Equipment grounding conductors never count.

Can I put 14 AWG wire on a 20 amp breaker?

No. NEC 240.4(D) limits 14 AWG copper to a 15 A breaker, 12 AWG to 20 A and 10 AWG to 30 A, even though the 75 °C column lists higher ampacities. The exceptions are specific loads such as motors and air-conditioning equipment (240.4(G)).

What size ground wire do I need?

The equipment grounding conductor is sized from the breaker rating in NEC Table 250.122: 14 AWG copper for a 15 A breaker, 12 AWG for 20 A, 10 AWG for 30 A to 60 A, 8 AWG for 100 A and 6 AWG for 200 A. If the circuit conductors are increased for voltage drop, the ground is increased in the same proportion (250.122(B)).

Is voltage drop part of wire sizing?

The NEC only recommends a voltage drop limit, 3% for a branch circuit, but on a long run it is often the step that decides the wire size. For a 24 A load 180 ft away at 240 V, ampacity asks for 10 AWG copper and a 3% voltage drop limit asks for 8 AWG.

More guides

Written by Andrii Zhukovskyi, a software developer and the maker of Electrician Calc. He is not a licensed electrician. The numbers follow NFPA 70, National Electrical Code, 2023 edition, and are the values the app uses (methodology and sources); the code text is not reproduced. Under the 2017 NEC, Table 310.16 is Table 310.15(B)(16), 310.15(C)(1) is 310.15(B)(3)(a) and 310.12 is 310.15(B)(7). Found a mistake? Write to [email protected]. Reference only: the edition and amendments adopted where you work, the equipment listing and the manufacturer's instructions govern. NEC® and NFPA 70® are registered trademarks of the National Fire Protection Association; this site is not affiliated with or endorsed by NFPA.