Voltage drop: 3% or 5%? What the NEC says and how to calculate it
The NEC (2023 edition) recommends no more than 3% voltage drop on a branch circuit and no more than 5% in total on the feeder plus the branch circuit. Both figures are in informational notes (to 210.19 and 215.2), so on most circuits an inspector cannot fail you for voltage drop. Limits are mandatory for fire pumps (695.7), technical power systems under Article 647, buildings under an energy code and equipment whose instructions set a minimum voltage. On 120 V, 3% is 3.6 V and 5% is 6 V. Single-phase voltage drop is VD = 2 × K × I × L ÷ CM, with K = 12.9 for copper, I the load current, L the one-way length in feet and CM the wire's area in circular mils.
Need the number for one run? The free voltage drop calculator works in the browser, and the Electrician Calc app does the same check offline on site. The rest of this page is the code behind 3% and 5%, the formula and two examples.
Is 3% voltage drop required by the NEC?
For most circuits, a 3% voltage drop is not an NEC requirement. The 3% and 5% figures are informational notes to NEC 210.19 (branch circuits) and 215.2 (feeders). Informational notes explain the code; under 90.5(C) they are not enforceable. An inspector can fail a general-purpose circuit for an undersized wire, but not for a 4% drop, unless a local amendment or an energy code says otherwise.
| Where | Limit | Required? | Source |
|---|---|---|---|
| Branch circuit | 3% | Recommended | NEC 210.19, informational note |
| Feeder | 3% | Recommended | NEC 215.2, informational note |
| Feeder plus branch circuit, total | 5% | Recommended | NEC 210.19 and 215.2, informational notes |
| Technical power systems for sensitive electronic equipment (120 V, 60 V to ground) | 1.5% branch, 2.5% feeder plus branch, for fixed equipment | Required | NEC 647.4(D) |
| Fire pump | 15% while the motor starts; 5% while it runs at 115% of full-load current | Required | NEC 695.7 |
| Commercial building under an energy code | 5% feeder plus branch | Required where adopted | IECC commercial provisions, ASHRAE 90.1 |
| Equipment with a stated minimum voltage | What the instructions say | Required | NEC 110.3(B) |
The 3% and 5% recommendation is still worth following, because the equipment at the end of the run only gets the voltage that is left. A motor on low voltage runs hotter. A resistance heater loses output with the square of the voltage, so a 5% drop means about 10% less heat. Lights dim when a compressor starts, and some electronics and EV chargers shut down when the voltage sags.
How many volts is a 3% or 5% voltage drop?
A 3% voltage drop is 3.6 V on a 120 V circuit and 7.2 V on a 240 V circuit; a 5% drop is 6.0 V and 12.0 V.
| System voltage | 3% drop | 5% drop | Left at the load after 3% |
|---|---|---|---|
| 120 V | 3.6 V | 6.0 V | 116.4 V |
| 208 V | 6.2 V | 10.4 V | 201.8 V |
| 240 V | 7.2 V | 12.0 V | 232.8 V |
| 277 V | 8.3 V | 13.9 V | 268.7 V |
| 480 V | 14.4 V | 24.0 V | 465.6 V |
How do you calculate voltage drop?
The formula most electricians use is the K-factor method:
Single phase: VD = 2 × K × I × L ÷ CM
Three phase: VD = 1.732 × K × I × L ÷ CM
K 12.9 for copper, 21.2 for aluminum
I load current, amps
L one-way length, feet
CM conductor area, circular mils (NEC Chapter 9, Table 8)
Percent drop = VD ÷ system voltage × 100
K is the resistance in ohms of one foot of wire one circular mil in area; 12.9 and 21.2 match copper and aluminum near their 75 °C operating temperature. Circular mils for the common sizes (NEC Chapter 9, Table 8): 14 AWG (14 gauge) is 4,110, 12 AWG is 6,530, 10 AWG is 10,380, 8 AWG is 16,510, 6 AWG is 26,240 and 4 AWG is 41,740. The formula ignores reactance, which is fine for branch circuits; for large AC feeders use the impedance values in Chapter 9, Table 9.
Three inputs cause most wrong answers:
- Current. Use the load the circuit carries, not the breaker rating. A 12 A load on a 20 A breaker drops 40% less than a 20 A load.
- Length. The formula takes the one-way length; the 2 covers the return path. Some calculators ask for the round trip instead, so check the label before you type. More on that in why two calculators give different answers.
- Voltage. Use the voltage of the circuit. The same current on the same wire is half the percentage at 240 V that it is at 120 V.
Example: what size wire for a 20 amp circuit 150 feet away?
A 120 V, 20 A circuit feeds a detached shop 150 ft from the panel. The tool on it draws 12 A. Copper wire.
| Wire | Calculation | Drop | 3% limit |
|---|---|---|---|
| 12 AWG | 2 × 12.9 × 12 × 150 ÷ 6,530 | 7.1 V, 5.9% | Fails |
| 10 AWG | 2 × 12.9 × 12 × 150 ÷ 10,380 | 4.5 V, 3.7% | Fails |
| 8 AWG | 2 × 12.9 × 12 × 150 ÷ 16,510 | 2.8 V, 2.3% | Passes |
12 AWG copper is legal for the 20 A breaker but loses almost 6% of the voltage at 150 ft. Keeping the drop under 3% takes 8 AWG. Because 3% is a recommendation, 10 AWG at 3.7% is also a legal choice.
If you go to 8 AWG, three things come with it:
- The ground goes up too. NEC 250.122(B) increases the equipment grounding conductor in proportion, here from 12 AWG to 8 AWG. 8/2 cable with a 10 AWG ground does not meet that, so run individual conductors or a cable with a full-size ground.
- Pigtails at the device. 8 AWG will not land on a receptacle, so splice it to short 12 AWG pigtails with a connector listed for that combination.
- Box fill. Each 8 AWG conductor counts 3.00 cubic inches: see box fill calculation.
If the tool can be wired for 240 V, there is a cheaper fix. It then draws 6 A instead of 12 A, and the same 12 AWG drops 3.6 V, which is 1.5% of 240 V.
The same check for other lengths: at a 3% drop on 120 V, 12 AWG copper reaches about 45 ft at a full 20 A, 57 ft at 16 A and 76 ft at 12 A, one way. See how far you can run 12 AWG on a 20 amp circuit and the wire size by amps and distance chart.
How do feeder and branch circuit voltage drop add up to 5%?
To check the 5% total, add the feeder's voltage drop percentage to the branch circuit's. Example: a garage subpanel 120 ft from the service on a 60 A, 240 V feeder in 6 AWG copper, with a calculated load of 48 A. From the subpanel, a 120 V circuit in 12 AWG runs 50 ft to a 12 A load.
- Feeder: 2 × 12.9 × 48 × 120 ÷ 26,240 = 5.7 V, which is 2.4% of 240 V.
- Branch: 2 × 12.9 × 12 × 50 ÷ 6,530 = 2.4 V, which is 2.0% of 120 V.
- Total: 4.3%. The branch is under 3% and the total is under 5%.
The 5% budget is shared between the feeder and the branch circuits: if the feeder alone drops 3%, every branch circuit it supplies has 2% left. Feeder sizes for this job are on the subpanel feeder wire size page.
How do you reduce voltage drop?
- Upsize the wire. One size up, such as 12 to 10 AWG, cuts the drop by about 37%. Two sizes up, 12 to 8 AWG, cuts it by about 60%. The ground goes up with it (250.122(B)); the full method is in how to size wire by the NEC, step by step.
- Raise the voltage. The same power at 240 V instead of 120 V is half the current, and the drop falls to a quarter in percent.
- Set a subpanel near the loads. The long run becomes one feeder sized for the distance and the branch circuits stay short.
- Split the load across two circuits.
Low-voltage DC runs need much larger wire for the same drop: see 12 V DC voltage drop.
In the browser: the voltage drop calculator and three-phase voltage drop.
Voltage drop questions
Is too much voltage drop an NEC violation?
Too much voltage drop is not an NEC violation on a general branch circuit or feeder. The 3% and 5% figures are informational notes to NEC 210.19 and 215.2, which are recommendations. It is a violation for fire pumps (695.7), Article 647 technical power systems (647.4(D)) and wherever an energy code or local amendment sets a limit.
What is the maximum voltage drop allowed by the NEC?
The NEC sets no general maximum voltage drop. It recommends 3% on a branch circuit and 5% for feeder plus branch circuit (informational notes to 210.19 and 215.2), and requires a limit only for fire pumps, Article 647 technical power systems and where an energy code or local amendment applies.
Do I calculate voltage drop with the breaker size or the load?
Calculate voltage drop with the load current the circuit is expected to carry, not the breaker rating. If the load is not known, the breaker rating gives the worst case, and 80% of the breaker rating is a common assumption for general-purpose circuits.
Do I enter the one-way distance or the round trip?
Enter the one-way length from the panel to the load when the formula contains the 2 (VD = 2 × K × I × L ÷ CM), because the 2 already accounts for the return conductor. Entering the round trip into that formula, or into a calculator built on it, doubles the result, so a real 3.0% drop shows as 6.0%.
Do I upsize the ground when I upsize the wire for voltage drop?
Yes. When the circuit conductors are increased in size for voltage drop, NEC 250.122(B) increases the equipment grounding conductor in proportion to their circular mil area. A 20 A circuit moved from 12 AWG to 8 AWG copper needs an 8 AWG ground instead of 12 AWG.
What is the voltage drop formula for three phase?
For three phase, VD = 1.732 × K × I × L ÷ CM, with K = 12.9 for copper or 21.2 for aluminum, I the line current, L the one-way length in feet and CM the circular mils from NEC Chapter 9, Table 8. Example: 40 A over 200 ft of 8 AWG copper at 480 V drops 1.732 × 12.9 × 40 × 200 ÷ 16,510 = 10.8 V, which is 2.3%.
How do I calculate voltage drop on a 12 V DC circuit?
Use the single-phase formula, VD = 2 × K × I × L ÷ CM, because DC current also flows out and back. 3% of 12 V is only 0.36 V, so 10 A over 20 ft one way drops 0.79 V (6.6%) on 12 AWG copper, 0.50 V (4.1%) on 10 AWG and 0.31 V (2.6%) on 8 AWG.
What K value do I use for aluminum?
Use K = 21.2 for aluminum, against 12.9 for copper. For the same voltage drop an aluminum conductor needs about 1.6 times the area of copper, which is usually two sizes larger.
More guides
- 8 AWG or 6 AWG for 50 amps?
- How to calculate box fill
- How to calculate conduit fill
- AWG vs mm²: which sizes are equivalent
- Continuous load: the 125% and 80% rules
- How to size wire step by step
Written by Andrii Zhukovskyi, a software developer and the maker of Electrician Calc. He is not a licensed electrician. The numbers follow NFPA 70, National Electrical Code, 2023 edition, and are the values the app uses (methodology and sources); the code text is not reproduced. Under the 2017 NEC, Table 310.16 is Table 310.15(B)(16), 310.15(C)(1) is 310.15(B)(3)(a) and 310.12 is 310.15(B)(7). Found a mistake? Write to [email protected]. Reference only: the edition and amendments adopted where you work, the equipment listing and the manufacturer's instructions govern. NEC® and NFPA 70® are registered trademarks of the National Fire Protection Association; this site is not affiliated with or endorsed by NFPA.