Continuous load and the 125% rule (the 80% breaker rule): when it changes the wire and the breaker

In short

Under the NEC (2023 edition), a continuous load is one whose maximum current is expected to continue for 3 hours or more (Article 100). The 125% rule sizes its wire and breaker at 125% of that current (210.19(A)(1) and 210.20(A) for branch circuits, 215.2(A)(1) and 215.3 for feeders). The 80% rule is the same rule read the other way: a standard breaker carries a continuous load of no more than 80% of its rating. EV chargers, storage water heaters and most commercial lighting are continuous; a household range, a clothes dryer and receptacle circuits in a house are not. A 40 A continuous load needs a 50 A breaker, while a range on a 40 A circuit stays on 40 A.

Leave the 125% out and a breaker runs at its limit for hours. Add it where it does not belong and a range ends up on a breaker one size too big. Here is which loads the rule covers and what it changes.

What is a continuous load, and which loads count?

The NEC defines a continuous load by time at maximum current: 3 hours or more (Article 100). For some equipment the code states the answer itself:

Which loads the NEC treats as continuous
LoadContinuous?Basis
EV charger (EVSE)YesNEC 625.42
Storage water heater, 120 gal or lessYesNEC 422.13
Fixed electric space heatingSized at 125% of the loadNEC 424.4(B)
Lighting in stores, offices and warehousesYes, it stays on for hoursArticle 100 definition
Solar PV circuitsYes: 125% of the 690.8(A) maximum current, which for PV source circuits is already 125% of Isc (156% in total)NEC 690.8
Household range, oven or cooktopNo, the elements cycleDoes not meet the Article 100 definition
Clothes dryerNoDoes not meet the Article 100 definition
General receptacle circuits in a houseNoDoes not meet the Article 100 definition
MotorOwn rule: conductors at 125% of the table full-load currentNEC 430.6, 430.22
Air conditioner or heat pumpUse the nameplate minimum circuit ampacity, which already includes the 125%NEC 440.4(B)

What is the 125% rule for continuous loads?

The conductor ampacity and the breaker rating must be at least 125% of the continuous load plus 100% of the non-continuous load on the same circuit:

minimum rating = 1.25 × continuous load + 1.00 × non-continuous load

Feeder with 40 A of lighting (continuous) and 30 A of receptacles:
1.25 × 40 + 30 = 80 A

The 125% requirement appears in five places: branch-circuit conductors (210.19(A)(1)), branch-circuit breakers (210.20(A)), feeder conductors (215.2(A)(1)), feeder breakers (215.3) and service conductors (230.42(A)). The main exception is an assembly listed for operation at 100% of its rating. In practice that means large breakers in listed enclosures, not the breakers in a house panel.

Is the 80% breaker rule the same as the 125% rule?

Yes. Sizing a breaker at 125% of the load and loading a breaker to 80% of its rating are the same calculation read in opposite directions, because 1 ÷ 1.25 = 0.8.

Largest continuous load on a standard breaker (80% of its rating)
BreakerLargest continuous load
15 A12 A
20 A16 A
30 A24 A
40 A32 A
50 A40 A
60 A48 A
100 A80 A
200 A160 A

The 125% rule is why a 48 A EV charger goes on a 60 A breaker and a 32 A charger on a 40 A. Wire sizes for chargers by amps and distance are on the EV charger wire size chart.

There is a separate 80% rule that people mix up with this one: a single cord-and-plug appliance that is not fastened in place may not draw more than 80% of a 15 A or 20 A branch circuit's rating, continuous or not (210.23).

When does the 125% rule change the breaker size and the wire size?

The 125% rule does not always change the wire or the breaker. The table compares the same load treated both ways, for copper THHN with 75 °C terminations (NEC Table 310.16, standard ratings from 240.6(A)):

Same load, non-continuous and continuous: breaker and copper THHN at 75 °C
LoadNot continuousContinuousWhat changed
16 A20 A breaker, 12 AWG20 A breaker, 12 AWGNothing
20 A20 A breaker, 12 AWG25 A breaker, 10 AWGBreaker and wire
24 A25 A breaker, 10 AWG30 A breaker, 10 AWGBreaker
30 A30 A breaker, 10 AWG40 A breaker, 8 AWGBreaker and wire
40 A40 A breaker, 8 AWG50 A breaker, 8 AWGBreaker
48 A50 A breaker, 8 AWG60 A breaker, 6 AWGBreaker and wire
80 A80 A breaker, 4 AWG100 A breaker, 3 AWGBreaker and wire

25 A is a standard rating, but most electricians do not stock it, so those rows usually end up on a 30 A breaker with the same 10 AWG wire. NM-B cable (Romex) uses the 60 °C column of Table 310.16 (334.80), so the wire goes up sooner: a 40 A continuous load needs 6 AWG in NM-B, and a 48 A one needs 4 AWG. To compare both answers for your own load, flip the continuous-load switch in the wire size calculator.

Common mistakes with the 125% rule

  • Left out. A 48 A charger on a 50 A breaker runs at 96% of the rating for hours. The result is a hot termination and a breaker that trips on warm days.
  • Applied to everything. My own app did this. Electrician Calc used to treat every load as continuous by default, so a range on a 40 A circuit came out on a 50 A breaker. A user test caught it, with an AI agent playing a US residential electrician sizing that range circuit: the tables were right, the default was wrong. The switch is now off by default and sits next to the load current. The story is in teaching an IEC calculator to speak NEC, and the same default is one of the reasons wire size calculators disagree.
  • Stacked on derating. The 125% is checked at the terminations without ambient or derating factors; those factors are checked against 100% of the load. NEC 210.19(A) makes these two separate checks and the larger wire wins. The full sequence is in how to size wire step by step.
  • Applied twice. The minimum circuit ampacity on an air conditioner's nameplate already includes the 125%. An EV charger sold for a 50 A circuit already charges at 40 A.

Continuous load questions

How long does a load have to run to be continuous?

A load is continuous when its maximum current is expected to last 3 hours or more, by the definition in NEC Article 100. A load that cycles on and off, like a range element, does not qualify even if the appliance is in use all evening.

How many amps can a 20 amp breaker carry continuously?

A 20 amp breaker carries 16 A continuously, which is 1,920 W at 120 V (80% of its rating, NEC 210.20(A)). A load that is not continuous may use the full 20 A, or 2,400 W. On a 15 A breaker the figures are 12 A and 1,440 W continuous.

Is an EV charger a continuous load?

Yes, an EV charger is a continuous load under NEC 625.42. A 48 A charger needs a 60 A breaker and 6 AWG copper THHN with 75 °C terminations, or 4 AWG in NM-B cable. A 40 A charger needs a 50 A breaker and a 32 A charger needs a 40 A breaker with 8 AWG copper.

Is a water heater a continuous load?

A storage water heater of 120 gallons or less is a continuous load under NEC 422.13. A 4,500 W, 240 V heater draws 18.75 A, and 125% of that is 23.4 A, so it goes on a 30 A breaker with 10 AWG copper, the standard water heater circuit. A 25 A breaker also complies, and 30 A is the maximum (150% of the rating, 422.11(E)(3)).

Is a kitchen range a continuous load?

No, a household range is not a continuous load. Its elements cycle, so the current does not stay at maximum for 3 hours. A 40 A range circuit uses a 40 A breaker and 8 AWG copper.

Do I use 125% of the load when I calculate voltage drop?

No. Voltage drop is calculated with the current the load actually draws. For a 48 A EV charger, the breaker and wire are sized for 60 A and the voltage drop is checked at 48 A; see voltage drop: 3% or 5%.

Does the 125% apply to the wire or to the breaker?

The 125% applies to both the wire and the breaker. NEC 210.19(A)(1) applies it to the branch-circuit conductors and 210.20(A) to the overcurrent device; 215.2(A)(1) and 215.3 do the same for feeders.

What is a 100% rated breaker?

A 100% rated breaker is one listed, together with its enclosure, to carry its full rating continuously, so the 125% rule does not apply to it. That marking is found on some large commercial breakers, not on standard residential ones.

More guides

Written by Andrii Zhukovskyi, a software developer and the maker of Electrician Calc. He is not a licensed electrician. The numbers follow NFPA 70, National Electrical Code, 2023 edition, and are the values the app uses (methodology and sources); the code text is not reproduced. Under the 2017 NEC, Table 310.16 is Table 310.15(B)(16), 310.15(C)(1) is 310.15(B)(3)(a) and 310.12 is 310.15(B)(7). Found a mistake? Write to [email protected]. Reference only: the edition and amendments adopted where you work, the equipment listing and the manufacturer's instructions govern. NEC® and NFPA 70® are registered trademarks of the National Fire Protection Association; this site is not affiliated with or endorsed by NFPA.