Target Superheat Calculator (Fixed Orifice)

Target superheat for a fixed-orifice (piston) air conditioner from the outdoor temperature and the indoor wet bulb, read from a manufacturer's superheat charging table.

Quick answer: at 95 °F outdoors and a 66 °F indoor wet bulb the table gives a target superheat of 10 °F; at 85 °F outdoors and the same wet bulb, 15 °F. Hotter outdoors means a lower target, more humid return air a higher one.

Outdoor: air entering the condenser. Indoor: wet bulb of the return air entering the evaporator coil.

Target superheat
–
In kelvin–
Table cells used–

Superheat charging table

Target superheat in °F at the low-side service port. Rows: outdoor dry bulb. Columns: wet bulb of the air entering the indoor coil. A dash means no target: do not charge by superheat there.

Outdoor °F \ indoor wet bulb °F5052545658606264666870727476
55912141720232629323537404245
60710121518212427303335384043
65–6101316192124273033363841
70––71013161921242730333639
75–––69121518212428313437
80––––581215182125283135
85––––––811151922263033
90––––––59131620242731
95–––––––6101418222529
100––––––––81215202327
105––––––––5913172226
110–––––––––611152025
115––––––––––8141823

Worked example: 92 °F outdoors, 65 °F indoor wet bulb

  1. 92 °F lies between the 90 °F and 95 °F rows, and 65 °F between the 64 °F and 66 °F columns.
  2. The four cells around the point are 9 and 13 °F (90 °F row), 6 and 10 °F (95 °F row).
  3. Interpolating between them on both axes gives 9.8 °F.

Result: target superheat of about 9.8 °F at the low-side service port.

Before you rely on it

This is one manufacturer's charging table for specific fixed-orifice units. Your unit's own charging chart and installation instructions come first. The source document also ties the table to indoor airflow close to the rated value, so check airflow before adjusting the charge.

The whole job, on your phone

HVAC Charge: Superheat & PT

Target superheat, actual superheat and a clear add or recover call in one screen, offline on the roof. See what's inside.

Questions

What is target superheat?

The superheat a fixed-orifice (piston) air conditioner should show at the suction service port when the charge is right. It changes with the load: the outdoor temperature and the wet bulb of the air entering the indoor coil.

How do I use the target?

Per the charging procedure in the source document: run the system at least 10 minutes, measure the actual superheat at the suction service port and compare it with the table. Higher than the target means the system needs refrigerant; lower means it has too much. Work out the actual superheat with the superheat calculator.

What does a dash in the table mean?

The manufacturer gives no superheat target for those conditions, so the charge must not be set by superheat there. Weigh in the charge instead, or wait for conditions inside the table.

Does this work for TXV or EEV systems?

No. An expansion valve holds superheat roughly constant, so those systems are charged by subcooling against the target on the unit's data plate.

Which wet bulb temperature do I use?

The wet bulb of the air entering the indoor (evaporator) coil, measured in the return air close to the unit. The outdoor temperature is the dry bulb of the air entering the condenser.

Is this table right for my unit?

It is one manufacturer's table, printed for Bryant 563C and 563G split systems. Other units have their own charging charts, often on the unit or in the installation instructions. Where your unit has its own chart, that chart governs.

Reference only. Charging targets and procedures come from the equipment manufacturer's data plate and installation instructions, and local codes apply. Handling refrigerants requires EPA Section 608 certification in the US.