EV charger wire size by amps and distance

Breaker and copper wire for 32, 40, 48 and 80 amp Level 2 chargers on 240 V, with the 125 % continuous-load rule and the voltage drop from 25 to 200 ft.

Quick answer: 48 A charger: 60 A breaker and 6 AWG copper for runs up to 150 ft. 40 A charger: 50 A breaker and 8 AWG copper for runs up to 100 ft. 32 A charger: 40 A breaker and 8 AWG copper for runs up to 100 ft. 80 A charger: 100 A breaker and 3 AWG copper for runs up to 150 ft. That is copper THHN in conduit on 75 °C terminals (NEC Table 310.16, 2023 edition), with voltage drop within 3 % on 240 V. The breaker is 125 % of the charger current, because the NEC treats charging as a continuous load (625.41).

In the Electrician Calc app: Wire Size is free and sizes the charger circuit for any current, length and wire type, with a switch for continuous loads. The EV Charger & Heat Pump Check (Pro) answers whether the existing service can take the charger, by NEC 220.83 or 220.87.

Checked by Andrii Zhukovskyi. Ampacities from NFPA 70, National Electrical Code, 2023 edition, Table 310.16; sizes and voltage drop computed with the formulas of the Electrician Calc app.

Breaker and wire for each charger

Charger current is what the charger draws, not the breaker. 240 V single phase, copper, 75 °C terminals, 30 °C ambient, no more than three current-carrying conductors. Short runs; see the next chart for length.

Charger current, power at 240 VBreaker (125 %)Copper THHN in conduitCopper NM-B cableCopper ground
32 A 7.7 kW40 A8 AWG8 AWG10 AWG
40 A 9.6 kW50 A8 AWG6 AWG10 AWG
48 A 11.5 kW60 A6 AWG4 AWG10 AWG
80 A 19.2 kW100 A3 AWG–8 AWG

Why other sites show a different number: the wiring method. THHN in conduit on 75 °C terminals is read from the 75 °C column, where 6 AWG copper is 65 A. NM-B cable is held to the 60 °C column (NEC 334.80), where 6 AWG is 55 A: less than the 60 A a 48 A charger needs, so NM-B has to be 4 AWG. NM-B is not made above 2 AWG (the dash in the chart), so an 80 A charger is wired with THHN in conduit. The ground is the minimum of NEC Table 250.122 for the breaker.

Copper THHN by run length

The smallest wire that carries the charger and keeps voltage drop at or under 3 % at the charger current, with the drop at that size. Length is one way.

One-way length32 A40 A48 A80 A
25 ft8 AWG 0.52 %8 AWG 0.65 %6 AWG 0.49 %3 AWG 0.41 %
50 ft8 AWG 1.05 %8 AWG 1.31 %6 AWG 0.99 %3 AWG 0.82 %
75 ft8 AWG 1.57 %8 AWG 1.96 %6 AWG 1.48 %3 AWG 1.23 %
100 ft8 AWG 2.09 %8 AWG 2.62 %6 AWG 1.98 %3 AWG 1.64 %
150 ft6 AWG 1.98 %6 AWG 2.47 %6 AWG 2.96 %3 AWG 2.46 %
200 ft6 AWG 2.63 %4 AWG 2.07 %4 AWG 2.48 %2 AWG 2.60 %

Worked example: 48 A charger, 200 ft from the panel, copper THHN in conduit

  1. Charging is a continuous load: 48 A × 125 % = 60 A, so the breaker is 60 A.
  2. By ampacity (75 °C column, NEC Table 310.16): 6 AWG copper, 65 A.
  3. Voltage drop of 6 AWG at 200 ft and 48 A: 3.95 % of 240 V. Over 3 %.
  4. Next size up, 4 AWG: 2.48 %. Under 3 %.
  5. Ground: Table 250.122 gives 10 AWG copper for a 60 A breaker; with the wire upsized from 6 AWG to 4 AWG, 250.122(B) increases it to 6 AWG.

Result: 4 AWG copper with a 6 AWG ground on a 60 A breaker.

Wire size calculator Wire size by amps and distance

Questions

What size wire for a 48 amp EV charger?

6 AWG copper THHN in conduit on a 60 A breaker, for runs up to 150 ft. In NM-B cable it has to be 4 AWG copper.

What size breaker for a 40 amp EV charger?

50 A: the charger is a continuous load, so the breaker is at least 125 % of 40 A. The wire is 8 AWG copper THHN in conduit, or 6 AWG copper NM-B.

What size wire for a 50 amp EV charger circuit?

A 50 A circuit carries a charger set to 40 A. It needs 8 AWG copper THHN in conduit or 6 AWG copper NM-B cable, larger on long runs: see the chart.

Can I use 6 AWG NM-B (Romex) for a 48 amp charger?

No. NM-B is limited to the 60 °C column, where 6 AWG copper is 55 A, and a 48 A charger needs a 60 A circuit. Use 4 AWG NM-B, or 6 AWG THHN in conduit, or set the charger to 40 A on a 50 A breaker.

Why 125 %?

An EV charger can run at full current for hours, so the NEC treats it as a continuous load: the breaker is rated at least 125 % of the charger's maximum current (NEC 625.41), and the conductors are sized for the same 125 % (210.19(A)(1)).

Does a longer run change the breaker?

No. The breaker follows the charger. A longer run only makes the wire larger to keep the voltage drop within 3 %.

Can my panel take the charger?

That is a separate question from the wire size: the existing service has to carry the new load. NEC 220.83 and 220.87 are the two ways to check an existing house. The EV Charger & Heat Pump Check in the Electrician Calc app (Pro) does both.

How are these sizes worked out?

The breaker is the next standard size at or above 125 % of the charger current. The wire is the smallest copper conductor whose ampacity in the 75 °C column of NEC Table 310.16 covers that, then upsized until the voltage drop at the charger current is 3 % or less on 240 V (K = 12.96 Ω·cmil/ft). These are the formulas of the wire size calculator on this site and of the Electrician Calc app.

Reference only. The code edition and amendments adopted where you work, the equipment's listing and the manufacturer's instructions govern. Have a licensed electrician check the installation.