PT chart · ASHRAE A1
R-134a PT Chart
R-134a pressure–temperature chart in psig and °F/°C. Medium-temp refrigeration, chillers, vehicles.
Vacuum readings are shown in inches of mercury (″ Hg) below atmospheric pressure.
| °F | °C | Pressure, psig |
|---|---|---|
| -50 | -45.6 | 18.7″ Hg |
| -45 | -42.8 | 16.9″ Hg |
| -40 | -40.0 | 14.8″ Hg |
| -35 | -37.2 | 12.5″ Hg |
| -30 | -34.4 | 9.8″ Hg |
| -25 | -31.7 | 6.9″ Hg |
| -20 | -28.9 | 3.7″ Hg |
| -15 | -26.1 | 0.0 |
| -10 | -23.3 | 1.9 |
| -5 | -20.6 | 4.1 |
| 0 | -17.8 | 6.5 |
| 5 | -15.0 | 9.1 |
| 10 | -12.2 | 11.9 |
| 15 | -9.4 | 15.0 |
| 20 | -6.7 | 18.4 |
| 25 | -3.9 | 22.1 |
| 30 | -1.1 | 26.1 |
| 35 | 1.7 | 30.4 |
| 40 | 4.4 | 35.0 |
| 45 | 7.2 | 40.1 |
| 50 | 10.0 | 45.4 |
| 55 | 12.8 | 51.2 |
| 60 | 15.6 | 57.4 |
| 65 | 18.3 | 64.0 |
| 70 | 21.1 | 71.1 |
| 75 | 23.9 | 78.7 |
| 80 | 26.7 | 86.7 |
| 85 | 29.4 | 95.2 |
| 90 | 32.2 | 104.3 |
| 95 | 35.0 | 114.0 |
| 100 | 37.8 | 124.2 |
| 105 | 40.6 | 135.0 |
| 110 | 43.3 | 146.4 |
| 115 | 46.1 | 158.4 |
| 120 | 48.9 | 171.2 |
| 125 | 51.7 | 184.6 |
| 130 | 54.4 | 198.7 |
| 135 | 57.2 | 213.6 |
| 140 | 60.0 | 229.2 |
| 145 | 62.8 | 245.7 |
| 150 | 65.6 | 262.9 |
Source: Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025). Reference only; verify against the equipment manufacturer's data.