Dre Dev Tools
Tools › HVAC › PT charts
PT chart · ASHRAE A1

R-410A PT Chart

R-410A pressure–temperature chart in psig and °F/°C. Residential and light commercial AC and heat pumps.

Vacuum readings are shown in inches of mercury (″ Hg) below atmospheric pressure.

Calculate superheat & subcooling with R-410A

°F°CPressure, psig
-50-45.65.0
-45-42.87.7
-40-40.010.8
-35-37.214.1
-30-34.417.8
-25-31.721.9
-20-28.926.3
-15-26.131.2
-10-23.336.5
-5-20.642.2
0-17.848.4
5-15.055.2
10-12.262.4
15-9.470.3
20-6.778.7
25-3.987.7
30-1.197.4
351.7107.7
404.4118.8
457.2130.6
5010.0143.2
5512.8156.5
6015.6170.7
6518.3185.8
7021.1201.8
7523.9218.7
8026.7236.5
8529.4255.4
9032.2275.4
9535.0296.4
10037.8318.6
10540.6341.9
11043.3366.4
11546.1392.3
12048.9419.4
12551.7447.9
13054.4477.9
13557.2509.4
14060.0542.5
14562.8577.3
15065.6613.9

Source: Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025). Reference only; verify against the equipment manufacturer's data.