Dre Dev Tools
Tools › HVAC › PT charts
PT chart · ASHRAE B2L

R-717 PT Chart

R-717 pressure–temperature chart in psig and °F/°C. Ammonia: industrial refrigeration. It is a B2L refrigerant (toxic, mildly flammable): for trained industrial technicians only.

Vacuum readings are shown in inches of mercury (″ Hg) below atmospheric pressure.

°F°CPressure, psig
-50-45.614.3″ Hg
-45-42.811.7″ Hg
-40-40.08.8″ Hg
-35-37.25.4″ Hg
-30-34.41.7″ Hg
-25-31.71.3
-20-28.93.6
-15-26.16.2
-10-23.39.0
-5-20.612.2
0-17.815.7
5-15.019.5
10-12.223.8
15-9.428.4
20-6.733.5
25-3.939.0
30-1.145.0
351.751.5
404.458.6
457.266.2
5010.074.5
5512.883.3
6015.692.9
6518.3103.1
7021.1114.1
7523.9125.8
8026.7138.4
8529.4151.7
9032.2166.0
9535.0181.1
10037.8197.2
10540.6214.3
11043.3232.4
11546.1251.5
12048.9271.7
12551.7293.1
13054.4315.7
13557.2339.5
14060.0364.5
14562.8390.8
15065.6418.5

Source: NIST Chemistry WebBook, SRD 69, saturation properties. Converted from absolute pressure (psia) to psig. Reference only; verify against the equipment manufacturer's data.

The whole job, on your phone

HVAC Charge: Superheat & PT

Look up R-717 offline in the field and get superheat, subcooling and a charge call in seconds. See what's inside.

Become a tester, freeiPhone? Sign upClosed test on Google Play · App Store coming soon

Other refrigerants