Dre Dev Tools
Tools › HVAC › PT charts
PT chart · ASHRAE A1

R-404A PT Chart

R-404A pressure–temperature chart in psig and °F/°C. Low and medium-temp commercial refrigeration.

Vacuum readings are shown in inches of mercury (″ Hg) below atmospheric pressure.

°F°CPressure, psig
-50-45.60.5
-45-42.82.6
-40-40.04.9
-35-37.27.5
-30-34.410.3
-25-31.713.4
-20-28.916.8
-15-26.120.5
-10-23.324.6
-5-20.628.9
0-17.833.7
5-15.038.8
10-12.244.3
15-9.450.2
20-6.756.6
25-3.963.4
30-1.170.7
351.778.6
404.486.9
457.295.8
5010.0105.3
5512.8115.3
6015.6126.0
6518.3137.3
7021.1149.3
7523.9162.0
8026.7175.4
8529.4189.5
9032.2204.5
9535.0220.2
10037.8236.8
10540.6254.2
11043.3272.5
11546.1291.8
12048.9312.1
12551.7333.3
13054.4355.7
13557.2379.1
14060.0403.7
14562.8429.6
15065.6456.8

Source: Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025). Reference only; verify against the equipment manufacturer's data.

The whole job, on your phone

HVAC Charge: Superheat & PT

Look up R-404A offline in the field and get superheat, subcooling and a charge call in seconds. See what's inside.

Become a tester, freeiPhone? Sign upClosed test on Google Play · App Store coming soon