Dre Dev Tools
Tools › HVAC › PT charts
PT chart · ASHRAE A2L

R-454B PT Chart

R-454B pressure–temperature chart in psig and °F/°C. New AC and heat pumps (R-410A replacement). It is an A2L (mildly flammable) refrigerant: follow A2L handling and equipment rules.

R-454B is a zeotropic blend with temperature glide, so the chart has two columns: use the vapor (dew) column for superheat and the liquid (bubble) column for subcooling.

Vacuum readings are shown in inches of mercury (″ Hg) below atmospheric pressure.

Calculate superheat & subcooling with R-454B

°F°CLiquid (bubble), psigVapor (dew), psig
-50-45.64.03.1
-45-42.86.65.6
-40-40.09.58.4
-35-37.212.711.4
-30-34.416.214.8
-25-31.720.118.5
-20-28.924.322.6
-15-26.128.927.0
-10-23.333.931.8
-5-20.639.437.0
0-17.845.342.7
5-15.051.748.8
10-12.258.555.4
15-9.466.062.6
20-6.773.970.3
25-3.982.578.5
30-1.191.787.4
351.7101.596.9
404.4112.0107.0
457.2123.1117.8
5010.0135.0129.3
5512.8147.7141.6
6015.6161.1154.6
6518.3175.4168.5
7021.1190.5183.1
7523.9206.5198.7
8026.7223.4215.2
8529.4241.2232.6
9032.2260.1251.0
9535.0279.9270.4
10037.8300.8290.9
10540.6322.8312.5
11043.3345.9335.2
11546.1370.2359.1
12048.9395.7384.3
12551.7422.4410.8
13054.4450.5438.7
13557.2479.9468.0
14060.0510.7498.8
14562.8543.0531.3
15065.6576.8565.4

Source: Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025). Reference only; verify against the equipment manufacturer's data.

The whole job, on your phone

HVAC Charge: Superheat & PT

Look up R-454B offline in the field and get superheat, subcooling and a charge call in seconds. See what's inside.

Become a tester, freeiPhone? Sign upClosed test on Google Play · App Store coming soon

Other refrigerants