Dre Dev Tools
Tools › HVAC › PT charts
PT chart · ASHRAE A2L

R-32 PT Chart

R-32 pressure–temperature chart in psig and °F/°C. AC, heat pumps and mini-splits. It is an A2L (mildly flammable) refrigerant: follow A2L handling and equipment rules.

Vacuum readings are shown in inches of mercury (″ Hg) below atmospheric pressure.

Calculate superheat & subcooling with R-32

°F°CPressure, psig
-50-45.65.2
-45-42.88.0
-40-40.011.0
-35-37.214.4
-30-34.418.2
-25-31.722.3
-20-28.926.8
-15-26.131.7
-10-23.337.1
-5-20.642.9
0-17.849.3
5-15.056.1
10-12.263.5
15-9.471.4
20-6.780.0
25-3.989.2
30-1.199.1
351.7109.7
404.4121.0
457.2133.0
5010.0145.9
5512.8159.5
6015.6174.1
6518.3189.5
7021.1205.8
7523.9223.2
8026.7241.5
8529.4260.9
9032.2281.3
9535.0302.9
10037.8325.7
10540.6349.7
11043.3374.9
11546.1401.4
12048.9429.3
12551.7458.7
13054.4489.5
13557.2521.8
14060.0555.8
14562.8591.4
15065.6628.8

Source: Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025). Reference only; verify against the equipment manufacturer's data.