12 V DC voltage drop and wire size chart
The smallest copper wire that keeps a 12 V DC run within 3 % or 10 % voltage drop, for 5 to 50 A over 5 to 50 ft.
Quick answer: at 12 V, 3 % is only 0.36 V. A 20 A load 15 ft from the battery needs 6 AWG copper to stay within 3 %, or 12 AWG if a 10 % drop is acceptable.
12 V DC wire size charts
Copper, AWG unless marked kcmil. Length is one way from the source to the load; both conductors are counted.
3 % voltage drop or less (0.36 V)
| Current \ one-way length | 5 ft | 10 ft | 15 ft | 20 ft | 25 ft | 30 ft | 40 ft | 50 ft |
|---|---|---|---|---|---|---|---|---|
| 5 A | 16 | 14 | 12 | 10 | 10 | 8 | 8 | 6 |
| 10 A | 14 | 10 | 8 | 8 | 6 | 6 | 4 | 4 |
| 15 A | 12 | 8 | 8 | 6 | 4 | 4 | 3 | 2 |
| 20 A | 10 | 8 | 6 | 4 | 4 | 3 | 2 | 1 |
| 30 A | 8 | 6 | 4 | 3 | 2 | 2 | 1/0 | 2/0 |
| 40 A | 8 | 4 | 3 | 2 | 1 | 1/0 | 2/0 | 3/0 |
| 50 A | 6 | 4 | 2 | 1 | 1/0 | 2/0 | 3/0 | 4/0 |
10 % voltage drop or less (1.2 V)
| Current \ one-way length | 5 ft | 10 ft | 15 ft | 20 ft | 25 ft | 30 ft | 40 ft | 50 ft |
|---|---|---|---|---|---|---|---|---|
| 5 A | 18 | 18 | 16 | 16 | 14 | 14 | 12 | 12 |
| 10 A | 18 | 16 | 14 | 12 | 12 | 12 | 10 | 8 |
| 15 A | 16 | 14 | 12 | 12 | 10 | 10 | 8 | 8 |
| 20 A | 16 | 12 | 12 | 10 | 8 | 8 | 6 | 6 |
| 30 A | 14 | 12 | 10 | 8 | 8 | 6 | 6 | 4 |
| 40 A | 12 | 10 | 8 | 6 | 6 | 6 | 4 | 3 |
| 50 A | 12 | 8 | 8 | 6 | 4 | 4 | 3 | 2 |
Voltage drop only. Check the wire's ampacity and the fuse rating separately. For 24 V the same wire allows twice the length.
Worked example: 20 A load, 15 ft from the battery, 12 V
- On 14 AWG: 2 × 15 ft of wire carry 20 A and drop 1.89 V, which is 15.8 % of 12 V.
- To stay within 3 % (0.36 V) the wire has to be 6 AWG: 2.47 %.
- If 10 % (1.2 V) is acceptable for the load, 12 AWG is enough: 9.93 %.
Result: 6 AWG for 3 %, 12 AWG for 10 %.
https://zhukovskyi.space/calculators/electrical/12v-dc-voltage-drop.html · checked 12 November 2026
Voltage drop calculator (choose DC)
Electrician Calc: Wire & Panel
DC, single and three-phase voltage drop, solar PV strings and battery sizing in one app. See what's inside.
Questions
Why does voltage drop matter more at 12 V?
The volts lost depend on current and wire, not on the system voltage. Losing 0.5 V is 0.4 % of 120 V but over 4 % of 12 V, so low-voltage DC runs need much heavier wire for the same percent.
What voltage drop is acceptable on 12 V?
It depends on the load, so this page gives two limits: 3 % (0.36 V) and 10 % (1.2 V). Use the limit the maker of the equipment specifies.
Is the length one way or round trip?
The tables use the one-way distance from the source to the load and already count both the positive and the negative conductor.
What size wire for 20 amps at 12 volts?
For a 15 ft run, 6 AWG keeps the drop within 3 % and 12 AWG within 10 %. Longer runs need larger wire: see the tables.
Does this cover fuse and ampacity?
No. These tables check voltage drop only. The wire must also be rated for the current, and the fuse or breaker must protect the wire. Vehicles and boats have their own wiring standards; follow the one that applies.
How is this calculated?
VD = 2 × K × I × L ÷ CM with K = 12.96 Ω·cmil/ft for copper: resistivity 0.017241 Ω·mm²/m at 20 °C plus 25 % for operating temperature, the resistance the voltage drop calculator on this site uses, set to DC. Cooler wire has slightly less resistance, so real drops are a little lower.
Reference only. The code edition and amendments adopted where you work, the equipment's listing and the manufacturer's instructions govern. Have a licensed electrician check the installation.