Dre Dev Tools
Tools › Electrical › 12 AWG voltage drop per foot
Electrical reference

12 AWG voltage drop per foot

How many volts 12 AWG copper loses per foot at 5 to 20 A, how far you can run it, and the same figure for 14 to 2 AWG.

Quick answer: 12 AWG copper drops about 3.97 mV per amp per foot of one-way length (single phase or DC). At 20 A that is 7.94 V per 100 ft, so a 120 V circuit reaches 3 % at about 45 ft.

Checked by Andrii Zhukovskyi. Computed with K = 12.96 Ω·cmil/ft for copper: resistivity 0.017241 Ω·mm²/m at 20 °C plus 25 % for operating temperature, the resistance the voltage drop calculator on this site uses.

12 AWG copper: voltage drop at 120 V

Volts lost and percent of 120 V. Length is one way; the formula counts both conductors. On 240 V the volts are the same and the percent is half.

Load \ one-way length25 ft50 ft75 ft100 ft150 ft200 ft
5 A0.50 V (0.4 %)0.99 V (0.8 %)1.49 V (1.2 %)1.99 V (1.7 %)2.98 V (2.5 %)3.97 V (3.3 %)
10 A0.99 V (0.8 %)1.99 V (1.7 %)2.98 V (2.5 %)3.97 V (3.3 %)5.96 V (5.0 %)7.94 V (6.6 %)
15 A1.49 V (1.2 %)2.98 V (2.5 %)4.47 V (3.7 %)5.96 V (5.0 %)8.93 V (7.4 %)11.91 V (9.9 %)
20 A1.99 V (1.7 %)3.97 V (3.3 %)5.96 V (5.0 %)7.94 V (6.6 %)11.91 V (9.9 %)15.88 V (13.2 %)

Voltage drop per amp per foot, 14 to 2 AWG

WireCopper, mV per amp per footAluminum, mV per amp per footCopper: longest run at 3 %, 120 V, full load
14 AWG6.308–38 ft at 15 A
12 AWG3.9716.50945 ft at 20 A
10 AWG2.4984.09548 ft at 30 A
8 AWG1.5702.57446 ft at 50 A
6 AWG0.9881.62056 ft at 65 A
4 AWG0.6211.01868 ft at 85 A
2 AWG0.3910.64180 ft at 115 A

Multiply by the amps and the one-way feet to get volts. Three phase: multiply the result by 0.866. The last column uses each size's usual breaker limit.

Worked example: 15 A on 12 AWG copper, 120 V, 80 ft

  1. Drop per amp per foot of one-way length: 3.971 mV.
  2. 3.971 mV × 15 A × 80 ft = 4.76 V.
  3. As a share of 120 V: 3.97 %.

Result: 4.76 V, over the 3 % recommendation.

Voltage drop calculator Wire size by amps and distance

The whole job, on your phone

Electrician Calc: Wire & Panel

Voltage drop, wire size and 21 calculators for NEC and IEC, with every step shown. See what's inside.

Questions

What is the voltage drop of 12 AWG wire per foot?

About 3.97 millivolts per amp for each foot of one-way length on a single-phase or DC circuit (copper, both conductors counted). At 20 A that is 0.0794 V per foot, or 7.94 V per 100 ft.

How far can I run 12 AWG on a 20 amp circuit?

About 45 ft one way at 120 V and 91 ft at 240 V before the drop passes 3 % at a full 20 A. At 15 A the 120 V distance is about 60 ft.

What is the voltage drop on 100 ft of 12 AWG at 20 amps?

7.94 V: 6.6 % at 120 V or 3.3 % at 240 V.

Is 3 % a code requirement?

For most circuits it is a recommendation in the NEC's informational notes (3 % on a branch circuit, 5 % for feeder and branch together), not a rule. Some equipment and some local codes do require it.

How is this calculated?

VD = 2 × K × I × L ÷ CM, with 6,530 circular mils for 12 AWG (NEC Chapter 9, Table 8) and K = 12.96 Ω·cmil/ft for copper: resistivity 0.017241 Ω·mm²/m at 20 °C plus 25 % for operating temperature, the resistance the voltage drop calculator on this site uses. That is 2 × 12.964 ÷ 6,530 = 3.971 mV per amp per foot. Handbooks often round K to 12.9, which gives 3.951 mV, about 0.5 % less.

Voltage drop only: the wire must also be large enough for the load and its breaker. Reference only. The code edition and amendments adopted where you work, the equipment's listing and the manufacturer's instructions govern. Have a licensed electrician check the installation.