Three-phase voltage drop: formula and chart
The 1.732 formula, the longest run at 3 % for 208, 240 and 480 V, and a worked example.
Quick answer: three-phase voltage drop is 1.732 × K × I × L ÷ CM, with K ≈ 12.9 for copper. It is 0.866 of the single-phase drop for the same wire, current and length. Example: 40 A on 8 AWG copper over 250 ft at 480 V drops 13.6 V (2.8 %).
Longest three-phase run at 3 % voltage drop
One-way length at the load shown (the 75 °C ampacity of each size from NEC Table 310.16), power factor 1.
| Wire | Load | 208 V copper | 240 V copper | 480 V copper | 480 V aluminum |
|---|---|---|---|---|---|
| 12 AWG | 20 A | 91 ft | 105 ft | 209 ft | 128 ft |
| 10 AWG | 30 A | 96 ft | 111 ft | 222 ft | 135 ft |
| 8 AWG | 50 A | 92 ft | 106 ft | 212 ft | 129 ft |
| 6 AWG | 65 A | 112 ft | 129 ft | 259 ft | 158 ft |
| 4 AWG | 85 A | 136 ft | 157 ft | 315 ft | 192 ft |
| 2 AWG | 115 A | 160 ft | 185 ft | 370 ft | 226 ft |
| 1/0 AWG | 150 A | 196 ft | 226 ft | 451 ft | 275 ft |
| 3/0 AWG | 200 A | 233 ft | 269 ft | 538 ft | 328 ft |
| 250 kcmil | 255 A | 272 ft | 314 ft | 629 ft | 384 ft |
| 500 kcmil | 380 A | 366 ft | 422 ft | 844 ft | 515 ft |
At half the load the length doubles. For 5 % multiply the length by 1.67.
Worked example: 40 A on 8 AWG copper, 480 V three phase, 250 ft
- Handbook K-factor (K = 12.9): VD = 1.732 × K × I × L ÷ CM = 1.732 × 12.9 × 40 A × 250 ft ÷ 16,510 cmil = 13.53 V.
- The calculator on this site uses K = 12.96 and gives 13.60 V line to line, which is 2.83 % of 480 V.
- The same wire, current and length on a single-phase circuit would drop 15.70 V: three phase is 0.866 of that.
Result: 13.60 V, 2.83 %, within 3 %.
https://zhukovskyi.space/calculators/electrical/three-phase-voltage-drop.html · checked 12 November 2026
Voltage drop calculator (choose 3-phase)
Electrician Calc: Wire & Panel
Three-phase cable sizing, motor circuits and fault level, NEC and IEC, with the working shown. See what's inside.
Questions
What is the three-phase voltage drop formula?
VD = 1.732 × K × I × L ÷ CM, with K ≈ 12.9 Ω·cmil/ft for copper in handbooks (this site's calculator uses 12.96 for copper and 21.3 for aluminum), I the line current, L the one-way length in feet and CM the conductor area in circular mils. The result is the drop between lines; divide by the line-to-line voltage for percent.
Why 1.732 instead of 2?
In a balanced three-phase circuit the currents in the three conductors cancel in the return path, so the line-to-line drop is √3 times the drop of one conductor, not twice as in a single-phase circuit.
Do I use line-to-line or line-to-neutral voltage?
Line-to-line with the 1.732 formula: 208, 240 or 480 V. For a single-phase load connected line to neutral on a three-phase system, use the single-phase formula with the line-to-neutral voltage.
How far can I run 6 AWG on a 480 V three-phase circuit?
About 259 ft one way at a full 65 A before the drop passes 3 %. At half the load the distance doubles.
Does power factor matter?
Yes, on large conductors and motor loads. The table assumes power factor 1; the voltage drop calculator on this site lets you enter the power factor and adds conductor reactance.
Voltage drop only: the wire must also be large enough for the load and its overcurrent protection. Reference only. The code edition and amendments adopted where you work, the equipment's listing and the manufacturer's instructions govern. Have a licensed electrician check the installation.