Three-phase voltage drop: formula and chart

The 1.732 formula, the longest run at 3 % for 208, 240 and 480 V, and a worked example.

Quick answer: three-phase voltage drop is 1.732 × K × I × L ÷ CM, with K ≈ 12.9 for copper. It is 0.866 of the single-phase drop for the same wire, current and length. Example: 40 A on 8 AWG copper over 250 ft at 480 V drops 13.6 V (2.8 %).

Checked by Andrii Zhukovskyi. Computed with K = 12.96 Ω·cmil/ft for copper: resistivity 0.017241 Ω·mm²/m at 20 °C plus 25 % for operating temperature, the resistance the voltage drop calculator on this site uses.

Longest three-phase run at 3 % voltage drop

One-way length at the load shown (the 75 °C ampacity of each size from NEC Table 310.16), power factor 1.

WireLoad208 V copper240 V copper480 V copper480 V aluminum
12 AWG20 A91 ft105 ft209 ft128 ft
10 AWG30 A96 ft111 ft222 ft135 ft
8 AWG50 A92 ft106 ft212 ft129 ft
6 AWG65 A112 ft129 ft259 ft158 ft
4 AWG85 A136 ft157 ft315 ft192 ft
2 AWG115 A160 ft185 ft370 ft226 ft
1/0 AWG150 A196 ft226 ft451 ft275 ft
3/0 AWG200 A233 ft269 ft538 ft328 ft
250 kcmil255 A272 ft314 ft629 ft384 ft
500 kcmil380 A366 ft422 ft844 ft515 ft

At half the load the length doubles. For 5 % multiply the length by 1.67.

Worked example: 40 A on 8 AWG copper, 480 V three phase, 250 ft

  1. Handbook K-factor (K = 12.9): VD = 1.732 × K × I × L ÷ CM = 1.732 × 12.9 × 40 A × 250 ft ÷ 16,510 cmil = 13.53 V.
  2. The calculator on this site uses K = 12.96 and gives 13.60 V line to line, which is 2.83 % of 480 V.
  3. The same wire, current and length on a single-phase circuit would drop 15.70 V: three phase is 0.866 of that.

Result: 13.60 V, 2.83 %, within 3 %.

Voltage drop calculator (choose 3-phase)

The whole job, on your phone

Electrician Calc: Wire & Panel

Three-phase cable sizing, motor circuits and fault level, NEC and IEC, with the working shown. See what's inside.

Questions

What is the three-phase voltage drop formula?

VD = 1.732 × K × I × L ÷ CM, with K ≈ 12.9 Ω·cmil/ft for copper in handbooks (this site's calculator uses 12.96 for copper and 21.3 for aluminum), I the line current, L the one-way length in feet and CM the conductor area in circular mils. The result is the drop between lines; divide by the line-to-line voltage for percent.

Why 1.732 instead of 2?

In a balanced three-phase circuit the currents in the three conductors cancel in the return path, so the line-to-line drop is √3 times the drop of one conductor, not twice as in a single-phase circuit.

Do I use line-to-line or line-to-neutral voltage?

Line-to-line with the 1.732 formula: 208, 240 or 480 V. For a single-phase load connected line to neutral on a three-phase system, use the single-phase formula with the line-to-neutral voltage.

How far can I run 6 AWG on a 480 V three-phase circuit?

About 259 ft one way at a full 65 A before the drop passes 3 %. At half the load the distance doubles.

Does power factor matter?

Yes, on large conductors and motor loads. The table assumes power factor 1; the voltage drop calculator on this site lets you enter the power factor and adds conductor reactance.

Voltage drop only: the wire must also be large enough for the load and its overcurrent protection. Reference only. The code edition and amendments adopted where you work, the equipment's listing and the manufacturer's instructions govern. Have a licensed electrician check the installation.