Refrigerant PT data: CSV and JSON
The pressure-temperature tables behind the PT charts and the superheat calculator on this site, as two files: 22 refrigerants, 883 rows, one row every 5 °F. Free to use with credit.
What is in the files
Saturation pressure at each temperature for 22 refrigerants. 9 of them are blends with two columns, liquid (bubble point) and vapor (dew point); the other 13 have one column. Both files hold the same rows. The JSON file also carries the column descriptions, the list of sources and one line per refrigerant.
refrigerant,safety_class,temp_f,temp_c,liquid_psig,vapor_psig,liquid_psia,vapor_psia,liquid_kpa,vapor_kpa,source R-410A,A1,-50,-45.56,5.0,,19.7,,135.8,,arkema-2025 R-410A,A1,-45,-42.78,7.7,,22.4,,154.4,,arkema-2025 R-410A,A1,-40,-40.0,10.8,,25.5,,175.8,,arkema-2025
Columns
| Column | Unit | Meaning |
|---|---|---|
refrigerant | – | ASHRAE designation, for example R-454B. |
safety_class | – | ASHRAE Standard 34 safety class as used on the chart pages (A1, A2L, A3, B2L). |
temp_f | °F | Saturation temperature. One row every 5 °F, as the source charts are printed. |
temp_c | °C | The same temperature in Celsius, rounded to 0.01. |
liquid_psig | psi, gauge | Liquid (bubble point) pressure. For a refrigerant with one column this is the saturation pressure. Negative means below atmospheric pressure. |
vapor_psig | psi, gauge | Vapor (dew point) pressure. Empty where the source prints one column, and for the few vapor cells left out (see below). |
liquid_psia | psi, absolute | liquid_psig + 14.695949. |
vapor_psia | psi, absolute | vapor_psig + 14.695949. |
liquid_kpa | kPa, absolute | liquid_psia × 6.894757. |
vapor_kpa | kPa, absolute | vapor_psia × 6.894757. |
source | – | Id of the source of the row; the sources are listed below and in the JSON file. |
Where the numbers come from
Nothing in the files was measured by me. 17 refrigerants are read from three published manufacturer tables; 5 are computed with the open-source CoolProp library. Each row names its source.
| Id in the files | Source | What the source says it is based on | Refrigerants | Retrieved |
|---|---|---|---|---|
arkema-2025 | Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025) | NIST REFPROP 10.0 (stated on the chart) | R-410A, R-454B, R-32, R-22, R-134a, R-404A, R-407C, R-448A, R-449A, R-452A, R-513A | 25 October 2026 |
arkema-2019 | Arkema Forane® Pressure-Temperature Wall Chart, Americas (2019) | NIST REFPROP 9.0 (stated on the chart) | R-407A, R-507A, R-427A, R-408A, R-409A | 25 October 2026 |
chemours-yf | Chemours, Thermodynamic Properties of Opteon™ YF, Engineering (I/P) Units | Manufacturer saturation table, 1 °F steps, psia | R-1234yf | 26 October 2026 |
coolprop | CoolProp 8.0.0, saturation pressure computed for this data set | Open-source property library (MIT licence); Helmholtz-energy equations of state from the literature | R-290, R-600a, R-744, R-717, R-12 | 20 November 2026 |
How the values got here:
- The Arkema charts print gauge pressure (psig) every 5 °F, and inches of mercury below one atmosphere for vacuum cells. A script read both PDFs cell by cell; the values were copied, not recalculated. In the files the vacuum cells are converted to negative psi (1 inHg = 0.4911541 psi), so one column has one unit.
- The Chemours table gives absolute pressure (psia). The 5 °F rows were kept and turned into gauge pressure by subtracting the standard atmosphere, 14.695949 psi, then rounded the way the printed charts are: to 0.1 psi above atmospheric pressure and to 0.1 inHg below it. The source itself gives more digits.
- R-290, R-600a, R-744, R-717, R-12 are computed: saturation pressure of the pure fluid at each temperature with CoolProp 8.0.0
(
PropsSI("P", "T", T, "Q", 0, fluid)), kept to 0.01 psi. The PT charts on this site for these five were read from the NIST Chemistry WebBook; the computed values agree with them within 0.04 psi, and the build stops if a row ever differs from its chart cell by more than rounding. The files carry the computed values so that every number in them is either a manufacturer's printed cell or the output of MIT-licensed software. - The absolute columns (
psia,kpa) andtemp_care plain unit conversions of the columns next to them. - R-427A is taken from the 2019 Arkema chart, because the 2025 edition prints two cells of another refrigerant in its 150 °F row.
- A few vapor cells of R-448A, R-449A and R-452A, and the rows of R-513A below −20 °F, are left out: the 2025 chart prints those vacuum cells in a unit that
does not match its legend, so they were not re-interpreted. That is why some
vapor_psigcells are empty and R-513A starts at −20 °F.
Checks, as listed in the methodology: Arkema's R-454B columns agree with Chemours' 1 °F table for Opteon™ XL41 within 0.06 psi, and values interpolated between rows agree with CoolProp 8.0 (NIST reference equations). No outside trade professional or laboratory has reviewed the files.
Refrigerants
| Refrigerant | Safety class | Columns | Range | Source |
|---|---|---|---|---|
| R-410A | A1 | One | -50 to 150 °F | arkema-2025 |
| R-454B | A2L | Liquid and vapor | -50 to 150 °F | arkema-2025 |
| R-32 | A2L | One | -50 to 150 °F | arkema-2025 |
| R-22 | A1 | One | -50 to 150 °F | arkema-2025 |
| R-134a | A1 | One | -50 to 150 °F | arkema-2025 |
| R-404A | A1 | One | -50 to 150 °F | arkema-2025 |
| R-407C | A1 | Liquid and vapor | -50 to 150 °F | arkema-2025 |
| R-407A | A1 | Liquid and vapor | -50 to 150 °F | arkema-2019 |
| R-448A | A1 | Liquid and vapor | -50 to 150 °F | arkema-2025 |
| R-449A | A1 | Liquid and vapor | -50 to 150 °F | arkema-2025 |
| R-452A | A1 | Liquid and vapor | -50 to 150 °F | arkema-2025 |
| R-513A | A1 | Liquid and vapor | -20 to 150 °F | arkema-2025 |
| R-1234yf | A2L | One | -50 to 150 °F | chemours-yf |
| R-507A | A1 | One | -50 to 150 °F | arkema-2019 |
| R-427A | A1 | Liquid and vapor | -50 to 150 °F | arkema-2019 |
| R-408A | A1 | One | -50 to 150 °F | arkema-2019 |
| R-409A | A1 | Liquid and vapor | -50 to 150 °F | arkema-2019 |
| R-290 | A3 | One | -50 to 150 °F | coolprop |
| R-600a | A3 | One | -50 to 150 °F | coolprop |
| R-744 | A1 | One | -50 to 85 °F | coolprop |
| R-717 | B2L | One | -50 to 150 °F | coolprop |
| R-12 | A1 | One | -50 to 150 °F | coolprop |
Licence
This compilation (the selection, the checks, the unit conversions, the file layout and the documentation) is published under Creative Commons Attribution 4.0 International (CC BY 4.0): copy it, change it and use it in any product, commercial ones included, as long as you give credit as shown below.
The values in the arkema-… and chemours-yf rows were published by Arkema and Chemours. I claim no rights in their
numbers and cannot grant any; if you republish the files, keep the source column so the origin stays visible. The coolprop
rows are my own computation with CoolProp (MIT licence) and are covered by the licence above.
How to cite
In text:
Andrii Zhukovskyi (2026). Refrigerant pressure-temperature (saturation) tables for 22 refrigerants (version 1.0.0) [Data set]. Dre Dev. https://zhukovskyi.space/calculators/hvac/refrigerant-pt-data.html
BibTeX:
@misc{zhukovskyi_refrigerant_pt_2026,
author = {Andrii Zhukovskyi},
title = {Refrigerant pressure-temperature (saturation) tables for 22 refrigerants},
year = {2026},
version = {1.0.0},
publisher = {Dre Dev},
howpublished = {\url{https://zhukovskyi.space/calculators/hvac/refrigerant-pt-data.html}},
note = {Data set, CC BY 4.0}
}
On a web page a link is enough: <a href="https://zhukovskyi.space/calculators/hvac/refrigerant-pt-data.html">Refrigerant PT data, Dre Dev</a>. If your work depends on
one refrigerant, cite the manufacturer's table or CoolProp from the list above as well.
Limits
Reference only. Charging targets and procedures come from the equipment manufacturer's data plate and installation instructions, and local codes apply. Handling refrigerants requires EPA Section 608 certification in the US.
The tables stop where the printed charts stop; there is no extrapolation. Gauge pressure assumes sea level. Version 1.0.0, published 20 November 2026. Corrections are listed in the changelog. Found a wrong cell? Send the refrigerant, the temperature and the source you compared with.