Dre Dev Tools
Tools › HVAC › Comparisons › R-407C vs R-22
Refrigerant comparison

R-407C vs R-22: pressures, glide and safety class

The published PT charts of R-407C and R-22 side by side at the same temperatures, with glide, safety class and GWP.

Quick answer: at the same temperatures R-407C runs at pressures close to, but not the same as, R-22. As saturated vapor at 40 °F, R-407C is 63.2 psig against 68.6 psig (-5.4 psi). As saturated liquid at 105 °F, R-407C is 242.4 psig against 210.8 psig (+31.6 psi, about 15 % higher).

Checked by Andrii Zhukovskyi. Pressures are cells of the Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025); differences are computed from them.

R-407C and R-22 pressure at the same temperature

Difference = R-407C minus R-22, in psi. Vacuum cells are in inches of mercury.

Suction side: saturated vapor (dew point) pressure

Temperature°CR-407C, psigR-22, psigDifference, psi
-40 °F-40.04.6″ Hg0.6-2.9
-20 °F-28.96.510.2-3.7
0 °F-17.819.424.0-4.6
20 °F-6.737.943.1-5.2
40 °F4.463.268.6-5.4
50 °F10.078.884.1-5.3
70 °F21.1117.3121.4-4.1
80 °F26.7140.5143.6-3.1
90 °F32.2166.7168.4-1.7
95 °F35.0181.0181.8-0.8
105 °F40.6212.1210.8+1.3
115 °F46.1246.9242.8+4.1
130 °F54.4306.7296.9+9.8

Liquid line: saturated liquid (bubble point) pressure

Temperature°CR-407C, psigR-22, psigDifference, psi
-40 °F-40.02.70.6+2.1
-20 °F-28.913.710.2+3.5
0 °F-17.829.524.0+5.5
20 °F-6.751.243.1+8.1
40 °F4.480.268.6+11.6
50 °F10.097.984.1+13.8
70 °F21.1140.5121.4+19.1
80 °F26.7165.8143.6+22.2
90 °F32.2194.1168.4+25.7
95 °F35.0209.4181.8+27.6
105 °F40.6242.4210.8+31.6
115 °F46.1279.0242.8+36.2
130 °F54.4340.7296.9+43.8

Same gauge reading, different saturation temperature

ReadingPressureR-407C saturationR-22 saturationError with the wrong chart
Suction gauge69 psig43.9 °F40.3 °F3.6 °F
Liquid gauge211 psig95.5 °F105.1 °F9.6 °F

Suction readings use the vapor (dew) column and liquid readings the liquid (bubble) column. The last column is how far off superheat or subcooling would be if the R-22 chart were used on R-407C, or the other way round.

R-407C and R-22 side by side

R-407CR-22
Safety classA1 (lower toxicity, no flame propagation)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026)A1 (lower toxicity, no flame propagation)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Refrigerated Food Processing and Dispensing Equipment (page updated 20 March 2026)
GWP (100-year)1,774 per US EPA (AR4, calculated for the blend)US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two.1,810 per US EPA (AR4)US EPA, Ozone-Depleting Substances (page updated 9 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two.
Temperature glide11.0 °F at a 40 °F dew point and 8.8 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart)None: a single-component refrigerant has one saturation temperature at each pressure.
Compressor lubricantPOE (polyolester)Arkema, 2025 Forane® Technical DigestMineral oil, alkylbenzene or POEArkema, 2025 Forane® Technical Digest
Sold as a replacement forR-22Arkema, 2025 Forane® Technical Digest–
Typical useAC and heat pumps (R-22 replacement)Older AC and heat pumps (phased out)
Pressure dataArkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025)Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025)
Ozone depletion potential–0.055US EPA, Ozone-Depleting Substances (page updated 9 April 2026)

Can R-407C replace R-22?

Arkema lists R-407C as a replacement and retrofit refrigerant for R-22 and says POE lubricant must be used with it (Arkema, 2025 Forane® Technical Digest).

A changeover follows the refrigerant maker's and the equipment maker's instructions. This page only compares the published pressure data.

Calculators and full charts

The whole job, on your phone

HVAC Charge: Superheat & PT

R-407C, R-22 and 20 more refrigerants on your phone, offline: superheat, subcooling and PT lookup. See what's inside.

Questions

Is R-407C higher or lower pressure than R-22?

At 105 °F saturated liquid R-407C is 242.4 psig and R-22 is 210.8 psig, a difference of +31.6 psi. At 40 °F saturated vapor it is 63.2 psig against 68.6 psig (-5.4 psi).

Can I use the R-22 PT chart for R-407C?

No. At 69 psig on the suction side the two charts give 43.9 °F for R-407C and 40.3 °F for R-22, so superheat would be off by 3.6 °F. At 211 psig on the liquid line subcooling would be off by 9.6 °F. Use the chart for the refrigerant in the system.

Which has more temperature glide, R-407C or R-22?

R-407C: 11.0 °F at a 40 °F dew point and 8.8 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart). R-22: none: a single-component refrigerant has one saturation temperature at each pressure..

Can R-407C replace R-22 in an existing system?

Arkema lists R-407C as a replacement and retrofit refrigerant for R-22 and says POE lubricant must be used with it (Arkema, 2025 Forane® Technical Digest). A changeover follows the refrigerant maker's and the equipment maker's instructions; this page only compares published pressure data.

Reference only. Charging targets and procedures come from the equipment manufacturer's data plate and installation instructions, and local codes apply. Handling refrigerants requires EPA Section 608 certification in the US.