R-454B vs R-32: pressures, glide and safety class

The published PT charts of R-454B and R-32 side by side at the same temperatures, with glide, safety class and GWP.

Quick answer: at the same temperatures R-454B runs at lower pressure than R-32. As saturated vapor at 40 °F, R-454B is 107.0 psig against 121.0 psig (-14.0 psi). As saturated liquid at 105 °F, R-454B is 322.8 psig against 349.7 psig (-26.9 psi, about 8 % lower).

Checked by Andrii Zhukovskyi. Pressures are cells of the Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025); differences are computed from them.

R-454B and R-32 pressure at the same temperature

Difference = R-454B minus R-32, in psi. Vacuum cells are in inches of mercury.

Suction side: saturated vapor (dew point) pressure

Temperature°CR-454B, psigR-32, psigDifference, psi
-40 °F-40.08.411.0-2.6
-20 °F-28.922.626.8-4.2
0 °F-17.842.749.3-6.6
20 °F-6.770.380.0-9.7
40 °F4.4107.0121.0-14.0
50 °F10.0129.3145.9-16.6
70 °F21.1183.1205.8-22.7
80 °F26.7215.2241.5-26.3
90 °F32.2251.0281.3-30.3
95 °F35.0270.4302.9-32.5
105 °F40.6312.5349.7-37.2
115 °F46.1359.1401.4-42.3
130 °F54.4438.7489.5-50.8

Liquid line: saturated liquid (bubble point) pressure

Temperature°CR-454B, psigR-32, psigDifference, psi
-40 °F-40.09.511.0-1.5
-20 °F-28.924.326.8-2.5
0 °F-17.845.349.3-4.0
20 °F-6.773.980.0-6.1
40 °F4.4112.0121.0-9.0
50 °F10.0135.0145.9-10.9
70 °F21.1190.5205.8-15.3
80 °F26.7223.4241.5-18.1
90 °F32.2260.1281.3-21.2
95 °F35.0279.9302.9-23.0
105 °F40.6322.8349.7-26.9
115 °F46.1370.2401.4-31.2
130 °F54.4450.5489.5-39.0

Same gauge reading, different saturation temperature

ReadingPressureR-454B saturationR-32 saturationError with the wrong chart
Suction gauge121 psig46.4 °F40.0 °F6.4 °F
Liquid gauge350 psig110.9 °F105.1 °F5.8 °F

Suction readings use the vapor (dew) column and liquid readings the liquid (bubble) column. The last column is how far off superheat or subcooling would be if the R-32 chart were used on R-454B, or the other way round.

R-454B and R-32 side by side

R-454BR-32
Safety classA2L (lower toxicity, lower flammability)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026)A2L (lower toxicity, lower flammability)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026)
CompositionR-32 / R-1234yf, 68.9 / 31.1 % by weightChemours, Opteon™ XL41 (R-454B) product information (C-11001, 7/24)–
GWP (100-year)465 per US EPA (AR4, calculated for the blend)US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two.675 per US EPA (IPCC 2007 (AR4))US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two.
Temperature glide2.3 °F at a 40 °F dew point and 2.3 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart)None: a single-component refrigerant has one saturation temperature at each pressure.
Compressor lubricantPOE (polyolester)Arkema, 2025 Forane® Technical DigestPOE (polyolester)Arkema, 2025 Forane® Technical Digest
Sold as a replacement forR-410A, in new equipment onlyArkema, 2025 Forane® Technical DigestR-410A, in new equipmentArkema, 2025 Forane® Technical Digest
Typical useNew AC and heat pumps (R-410A replacement)AC, heat pumps and mini-splits
Pressure dataArkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025)Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025)

Can R-454B replace R-32?

Both are A2L refrigerants that Arkema lists as R-410A replacements for new equipment (Arkema, 2025 Forane® Technical Digest). They are not interchangeable: a unit is built, listed and charged for one of them, named on its data plate.

A changeover follows the refrigerant maker's and the equipment maker's instructions. This page only compares the published pressure data.

Calculators and full charts

The whole job, on your phone

HVAC Charge: Superheat & PT

R-454B, R-32 and 20 more refrigerants on your phone, offline: superheat, subcooling and PT lookup. See what's inside.

Questions

Is R-454B higher or lower pressure than R-32?

At 105 °F saturated liquid R-454B is 322.8 psig and R-32 is 349.7 psig, a difference of -26.9 psi. At 40 °F saturated vapor it is 107.0 psig against 121.0 psig (-14.0 psi).

Can I use the R-32 PT chart for R-454B?

No. At 121 psig on the suction side the two charts give 46.4 °F for R-454B and 40.0 °F for R-32, so superheat would be off by 6.4 °F. At 350 psig on the liquid line subcooling would be off by 5.8 °F. Use the chart for the refrigerant in the system.

Which has more temperature glide, R-454B or R-32?

R-454B: 2.3 °F at a 40 °F dew point and 2.3 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart). R-32: none: a single-component refrigerant has one saturation temperature at each pressure..

Can R-454B replace R-32 in an existing system?

Both are A2L refrigerants that Arkema lists as R-410A replacements for new equipment (Arkema, 2025 Forane® Technical Digest). They are not interchangeable: a unit is built, listed and charged for one of them, named on its data plate. A changeover follows the refrigerant maker's and the equipment maker's instructions; this page only compares published pressure data.

Reference only. Charging targets and procedures come from the equipment manufacturer's data plate and installation instructions, and local codes apply. Handling refrigerants requires EPA Section 608 certification in the US.