Dre Dev Tools
Tools › HVAC › Comparisons › R-448A vs R-404A
Refrigerant comparison

R-448A vs R-404A: pressures, glide and safety class

The published PT charts of R-448A and R-404A side by side at the same temperatures, with glide, safety class and GWP.

Quick answer: at the same temperatures R-448A runs at pressures close to, but not the same as, R-404A. As saturated vapor at 40 °F, R-448A is 72.1 psig against 86.9 psig (-14.8 psi). As saturated liquid at 105 °F, R-448A is 261.7 psig against 254.2 psig (+7.5 psi, about 3 % higher).

Checked by Andrii Zhukovskyi. Pressures are cells of the Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025); differences are computed from them.

R-448A and R-404A pressure at the same temperature

Difference = R-448A minus R-404A, in psi. Vacuum cells are in inches of mercury.

Suction side: saturated vapor (dew point) pressure

Temperature°CR-448A, psigR-404A, psigDifference, psi
-40 °F-40.00.04.9-4.9
-20 °F-28.99.816.8-7.0
0 °F-17.824.333.7-9.4
20 °F-6.744.656.6-12.0
40 °F4.472.186.9-14.8
50 °F10.089.0105.3-16.3
70 °F21.1130.3149.3-19.0
80 °F26.7155.1175.4-20.3
90 °F32.2183.0204.5-21.5
95 °F35.0198.2220.2-22.0
105 °F40.6231.3254.2-22.9
115 °F46.1268.1291.8-23.7
130 °F54.4331.3355.7-24.4

Liquid line: saturated liquid (bubble point) pressure

Temperature°CR-448A, psigR-404A, psigDifference, psi
-40 °F-40.04.94.9+0.0
-20 °F-28.917.016.8+0.2
0 °F-17.834.233.7+0.5
20 °F-6.757.856.6+1.2
40 °F4.489.086.9+2.1
50 °F10.0108.0105.3+2.7
70 °F21.1153.5149.3+4.2
80 °F26.7180.5175.4+5.1
90 °F32.2210.5204.5+6.0
95 °F35.0226.7220.2+6.5
105 °F40.6261.7254.2+7.5
115 °F46.1300.2291.8+8.4
130 °F54.4365.3355.7+9.6

Same gauge reading, different saturation temperature

ReadingPressureR-448A saturationR-404A saturationError with the wrong chart
Suction gauge87 psig48.9 °F40.1 °F8.8 °F
Liquid gauge254 psig102.9 °F104.9 °F2.1 °F

Suction readings use the vapor (dew) column and liquid readings the liquid (bubble) column. The last column is how far off superheat or subcooling would be if the R-404A chart were used on R-448A, or the other way round.

R-448A and R-404A side by side

R-448AR-404A
Safety classA1 (lower toxicity, no flame propagation)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Refrigerated Food Processing and Dispensing Equipment (page updated 20 March 2026)A1 (lower toxicity, no flame propagation)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026)
GWP (100-year)1,386 per US EPA (AR4, calculated for the blend)US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two.3,922 per US EPA (AR4, calculated for the blend)US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two.
Temperature glide10.1 °F at a 40 °F dew point and 8.3 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart)The source chart prints one pressure column, used for both superheat and subcooling.
Compressor lubricantPOE (polyolester)Arkema, 2025 Forane® Technical DigestPOE (polyolester)Arkema, 2025 Forane® Technical Digest
Sold as a replacement forR-404A, R-507A, R-22 and the R-407 seriesArkema, 2025 Forane® Technical DigestR-502Arkema, 2025 Forane® Technical Digest
Typical useLow and medium-temp refrigeration (R-404A replacement)Low and medium-temp commercial refrigeration
Pressure dataArkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025)Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025)

Can R-448A replace R-404A?

Arkema describes R-448A as designed to replace R-404A, R-507A, R-22 and the R-407 series, typically with POE oil (Arkema, 2025 Forane® Technical Digest).

A changeover follows the refrigerant maker's and the equipment maker's instructions. This page only compares the published pressure data.

Calculators and full charts

The whole job, on your phone

HVAC Charge: Superheat & PT

R-448A, R-404A and 20 more refrigerants on your phone, offline: superheat, subcooling and PT lookup. See what's inside.

Questions

Is R-448A higher or lower pressure than R-404A?

At 105 °F saturated liquid R-448A is 261.7 psig and R-404A is 254.2 psig, a difference of +7.5 psi. At 40 °F saturated vapor it is 72.1 psig against 86.9 psig (-14.8 psi).

Can I use the R-404A PT chart for R-448A?

No. At 87 psig on the suction side the two charts give 48.9 °F for R-448A and 40.1 °F for R-404A, so superheat would be off by 8.8 °F. At 254 psig on the liquid line subcooling would be off by 2.1 °F. Use the chart for the refrigerant in the system.

Which has more temperature glide, R-448A or R-404A?

R-448A: 10.1 °F at a 40 °F dew point and 8.3 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart). R-404A: the source chart prints one pressure column, used for both superheat and subcooling..

Can R-448A replace R-404A in an existing system?

Arkema describes R-448A as designed to replace R-404A, R-507A, R-22 and the R-407 series, typically with POE oil (Arkema, 2025 Forane® Technical Digest). A changeover follows the refrigerant maker's and the equipment maker's instructions; this page only compares published pressure data.

Reference only. Charging targets and procedures come from the equipment manufacturer's data plate and installation instructions, and local codes apply. Handling refrigerants requires EPA Section 608 certification in the US.