R-454B vs R-410A: pressures, glide and safety class
The published PT charts of R-454B and R-410A side by side at the same temperatures, with glide, safety class and GWP.
Quick answer: at the same temperatures R-454B runs at lower pressure than R-410A. As saturated vapor at 40 °F, R-454B is 107.0 psig against 118.8 psig (-11.8 psi). As saturated liquid at 105 °F, R-454B is 322.8 psig against 341.9 psig (-19.1 psi, about 6 % lower).
R-454B and R-410A pressure at the same temperature
Difference = R-454B minus R-410A, in psi. Vacuum cells are in inches of mercury.
Suction side: saturated vapor (dew point) pressure
| Temperature | °C | R-454B, psig | R-410A, psig | Difference, psi |
|---|---|---|---|---|
| -40 °F | -40.0 | 8.4 | 10.8 | -2.4 |
| -20 °F | -28.9 | 22.6 | 26.3 | -3.7 |
| 0 °F | -17.8 | 42.7 | 48.4 | -5.7 |
| 20 °F | -6.7 | 70.3 | 78.7 | -8.4 |
| 40 °F | 4.4 | 107.0 | 118.8 | -11.8 |
| 50 °F | 10.0 | 129.3 | 143.2 | -13.9 |
| 70 °F | 21.1 | 183.1 | 201.8 | -18.7 |
| 80 °F | 26.7 | 215.2 | 236.5 | -21.3 |
| 90 °F | 32.2 | 251.0 | 275.4 | -24.4 |
| 95 °F | 35.0 | 270.4 | 296.4 | -26.0 |
| 105 °F | 40.6 | 312.5 | 341.9 | -29.4 |
| 115 °F | 46.1 | 359.1 | 392.3 | -33.2 |
| 130 °F | 54.4 | 438.7 | 477.9 | -39.2 |
Liquid line: saturated liquid (bubble point) pressure
| Temperature | °C | R-454B, psig | R-410A, psig | Difference, psi |
|---|---|---|---|---|
| -40 °F | -40.0 | 9.5 | 10.8 | -1.3 |
| -20 °F | -28.9 | 24.3 | 26.3 | -2.0 |
| 0 °F | -17.8 | 45.3 | 48.4 | -3.1 |
| 20 °F | -6.7 | 73.9 | 78.7 | -4.8 |
| 40 °F | 4.4 | 112.0 | 118.8 | -6.8 |
| 50 °F | 10.0 | 135.0 | 143.2 | -8.2 |
| 70 °F | 21.1 | 190.5 | 201.8 | -11.3 |
| 80 °F | 26.7 | 223.4 | 236.5 | -13.1 |
| 90 °F | 32.2 | 260.1 | 275.4 | -15.3 |
| 95 °F | 35.0 | 279.9 | 296.4 | -16.5 |
| 105 °F | 40.6 | 322.8 | 341.9 | -19.1 |
| 115 °F | 46.1 | 370.2 | 392.3 | -22.1 |
| 130 °F | 54.4 | 450.5 | 477.9 | -27.4 |
Same gauge reading, different saturation temperature
| Reading | Pressure | R-454B saturation | R-410A saturation | Error with the wrong chart |
|---|---|---|---|---|
| Suction gauge | 119 psig | 45.5 °F | 40.1 °F | 5.4 °F |
| Liquid gauge | 342 psig | 109.2 °F | 105.0 °F | 4.2 °F |
Suction readings use the vapor (dew) column and liquid readings the liquid (bubble) column. The last column is how far off superheat or subcooling would be if the R-410A chart were used on R-454B, or the other way round.
R-454B and R-410A side by side
| R-454B | R-410A | |
|---|---|---|
| Safety class | A2L (lower toxicity, lower flammability)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026) | A1 (lower toxicity, no flame propagation)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026) |
| Composition | R-32 / R-1234yf, 68.9 / 31.1 % by weightChemours, Opteon™ XL41 (R-454B) product information (C-11001, 7/24) | – |
| GWP (100-year) | 465 per US EPA (AR4, calculated for the blend)US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two. | 2,088 per US EPA (AR4, calculated for the blend)US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two. |
| Temperature glide | 2.3 °F at a 40 °F dew point and 2.3 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart) | The source chart prints one pressure column, used for both superheat and subcooling. |
| Compressor lubricant | POE (polyolester)Arkema, 2025 Forane® Technical Digest | POE (polyolester)Arkema, 2025 Forane® Technical Digest |
| Sold as a replacement for | R-410A, in new equipment onlyArkema, 2025 Forane® Technical Digest | – |
| Typical use | New AC and heat pumps (R-410A replacement) | Residential and light commercial AC and heat pumps |
| Pressure data | Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025) | Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025) |
Can R-454B replace R-410A?
R-454B is not a top-off or retrofit refrigerant for R-410A equipment. Chemours' R-454B guide says A2L refrigerants are for new equipment only (Chemours, Opteon™ XL41 (R-454B) Pressure-Temperature Guide for A/C), and Arkema lists R-454B as an R-410A replacement for new equipment (Arkema, 2025 Forane® Technical Digest). York's R-454B manual has the outdoor unit, indoor coil and metering device replaced together when an R-410A system is replaced (York YH9/XH9 R-454B heat pump Installation Manual 6515371-UIM-B-0526).
A changeover follows the refrigerant maker's and the equipment maker's instructions. This page only compares the published pressure data.
Calculators and full charts
HVAC Charge: Superheat & PT
R-454B, R-410A and 20 more refrigerants on your phone, offline: superheat, subcooling and PT lookup. See what's inside.
Questions
Is R-454B higher or lower pressure than R-410A?
At 105 °F saturated liquid R-454B is 322.8 psig and R-410A is 341.9 psig, a difference of -19.1 psi. At 40 °F saturated vapor it is 107.0 psig against 118.8 psig (-11.8 psi).
Can I use the R-410A PT chart for R-454B?
No. At 119 psig on the suction side the two charts give 45.5 °F for R-454B and 40.1 °F for R-410A, so superheat would be off by 5.4 °F. At 342 psig on the liquid line subcooling would be off by 4.2 °F. Use the chart for the refrigerant in the system.
Which has more temperature glide, R-454B or R-410A?
R-454B: 2.3 °F at a 40 °F dew point and 2.3 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart). R-410A: the source chart prints one pressure column, used for both superheat and subcooling..
Can R-454B replace R-410A in an existing system?
R-454B is not a top-off or retrofit refrigerant for R-410A equipment. Chemours' R-454B guide says A2L refrigerants are for new equipment only (Chemours, Opteon™ XL41 (R-454B) Pressure-Temperature Guide for A/C), and Arkema lists R-454B as an R-410A replacement for new equipment (Arkema, 2025 Forane® Technical Digest). York's R-454B manual has the outdoor unit, indoor coil and metering device replaced together when an R-410A system is replaced (York YH9/XH9 R-454B heat pump Installation Manual 6515371-UIM-B-0526). A changeover follows the refrigerant maker's and the equipment maker's instructions; this page only compares published pressure data.
Reference only. Charging targets and procedures come from the equipment manufacturer's data plate and installation instructions, and local codes apply. Handling refrigerants requires EPA Section 608 certification in the US.
https://zhukovskyi.space/calculators/hvac/compare/r-454b-vs-r-410a.html · checked 12 November 2026