R-513A vs R-134a: pressures, glide and safety class
The published PT charts of R-513A and R-134a side by side at the same temperatures, with glide, safety class and GWP.
Quick answer: at the same temperatures R-513A runs at higher pressure than R-134a. As saturated vapor at 40 °F, R-513A is 40.1 psig against 35.0 psig (+5.1 psi). As saturated liquid at 105 °F, R-513A is 143.1 psig against 135.0 psig (+8.1 psi, about 6 % higher).
R-513A and R-134a pressure at the same temperature
Difference = R-513A minus R-134a, in psi. Vacuum cells are in inches of mercury.
Suction side: saturated vapor (dew point) pressure
| Temperature | °C | R-513A, psig | R-134a, psig | Difference, psi |
|---|---|---|---|---|
| -20 °F | -28.9 | 0.4 | 3.7″ Hg | +2.2 |
| 0 °F | -17.8 | 9.5 | 6.5 | +3.0 |
| 20 °F | -6.7 | 22.4 | 18.4 | +4.0 |
| 40 °F | 4.4 | 40.1 | 35.0 | +5.1 |
| 50 °F | 10.0 | 51.0 | 45.4 | +5.6 |
| 70 °F | 21.1 | 77.7 | 71.1 | +6.6 |
| 80 °F | 26.7 | 93.8 | 86.7 | +7.1 |
| 90 °F | 32.2 | 111.9 | 104.3 | +7.6 |
| 95 °F | 35.0 | 121.7 | 114.0 | +7.7 |
| 105 °F | 40.6 | 143.1 | 135.0 | +8.1 |
| 115 °F | 46.1 | 166.9 | 158.4 | +8.5 |
| 130 °F | 54.4 | 207.5 | 198.7 | +8.8 |
Liquid line: saturated liquid (bubble point) pressure
| Temperature | °C | R-513A, psig | R-134a, psig | Difference, psi |
|---|---|---|---|---|
| -20 °F | -28.9 | 0.5 | 3.7″ Hg | +2.3 |
| 0 °F | -17.8 | 9.6 | 6.5 | +3.1 |
| 20 °F | -6.7 | 22.5 | 18.4 | +4.1 |
| 40 °F | 4.4 | 40.1 | 35.0 | +5.1 |
| 50 °F | 10.0 | 51.1 | 45.4 | +5.7 |
| 70 °F | 21.1 | 77.7 | 71.1 | +6.6 |
| 80 °F | 26.7 | 93.8 | 86.7 | +7.1 |
| 90 °F | 32.2 | 111.9 | 104.3 | +7.6 |
| 95 °F | 35.0 | 121.7 | 114.0 | +7.7 |
| 105 °F | 40.6 | 143.1 | 135.0 | +8.1 |
| 115 °F | 46.1 | 166.9 | 158.4 | +8.5 |
| 130 °F | 54.4 | 207.5 | 198.7 | +8.8 |
Same gauge reading, different saturation temperature
| Reading | Pressure | R-513A saturation | R-134a saturation | Error with the wrong chart |
|---|---|---|---|---|
| Suction gauge | 35 psig | 34.8 °F | 40.0 °F | 5.2 °F |
| Liquid gauge | 135 psig | 101.3 °F | 105.0 °F | 3.7 °F |
Suction readings use the vapor (dew) column and liquid readings the liquid (bubble) column. The last column is how far off superheat or subcooling would be if the R-134a chart were used on R-513A, or the other way round.
R-513A and R-134a side by side
| R-513A | R-134a | |
|---|---|---|
| Safety class | A1 (lower toxicity, no flame propagation)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026) | A1 (lower toxicity, no flame propagation)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026) |
| GWP (100-year) | 630 per US EPA (AR4, calculated for the blend)US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two. | 1,430 per US EPA (IPCC 2007 (AR4))US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two. |
| Temperature glide | 0.0 °F at a 40 °F dew point and 0.0 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart) | None: a single-component refrigerant has one saturation temperature at each pressure. |
| Compressor lubricant | POE (polyolester)Arkema, 2025 Forane® Technical Digest | POE; PAG in automotive AC onlyArkema, 2025 Forane® Technical Digest |
| Sold as a replacement for | R-134a, except in automotive ACArkema, 2025 Forane® Technical Digest | R-12Arkema, 2025 Forane® Technical Digest |
| Typical use | Medium-temp refrigeration and chillers (R-134a replacement) | Medium-temp refrigeration, chillers, vehicles |
| Pressure data | Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025) | Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025) |
Can R-513A replace R-134a?
Arkema lists R-513A as a replacement for R-134a, except in automotive AC, typically with POE oil (Arkema, 2025 Forane® Technical Digest).
A changeover follows the refrigerant maker's and the equipment maker's instructions. This page only compares the published pressure data.
Calculators and full charts
HVAC Charge: Superheat & PT
R-513A, R-134a and 20 more refrigerants on your phone, offline: superheat, subcooling and PT lookup. See what's inside.
Questions
Is R-513A higher or lower pressure than R-134a?
At 105 °F saturated liquid R-513A is 143.1 psig and R-134a is 135.0 psig, a difference of +8.1 psi. At 40 °F saturated vapor it is 40.1 psig against 35.0 psig (+5.1 psi).
Can I use the R-134a PT chart for R-513A?
No. At 35 psig on the suction side the two charts give 34.8 °F for R-513A and 40.0 °F for R-134a, so superheat would be off by 5.2 °F. At 135 psig on the liquid line subcooling would be off by 3.7 °F. Use the chart for the refrigerant in the system.
Which has more temperature glide, R-513A or R-134a?
R-513A: 0.0 °F at a 40 °F dew point and 0.0 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart). R-134a: none: a single-component refrigerant has one saturation temperature at each pressure..
Can R-513A replace R-134a in an existing system?
Arkema lists R-513A as a replacement for R-134a, except in automotive AC, typically with POE oil (Arkema, 2025 Forane® Technical Digest). A changeover follows the refrigerant maker's and the equipment maker's instructions; this page only compares published pressure data.
Reference only. Charging targets and procedures come from the equipment manufacturer's data plate and installation instructions, and local codes apply. Handling refrigerants requires EPA Section 608 certification in the US.