Dre Dev Tools
Tools › HVAC › Comparisons › R-513A vs R-134a
Refrigerant comparison

R-513A vs R-134a: pressures, glide and safety class

The published PT charts of R-513A and R-134a side by side at the same temperatures, with glide, safety class and GWP.

Quick answer: at the same temperatures R-513A runs at higher pressure than R-134a. As saturated vapor at 40 °F, R-513A is 40.1 psig against 35.0 psig (+5.1 psi). As saturated liquid at 105 °F, R-513A is 143.1 psig against 135.0 psig (+8.1 psi, about 6 % higher).

Checked by Andrii Zhukovskyi. Pressures are cells of the Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025); differences are computed from them.

R-513A and R-134a pressure at the same temperature

Difference = R-513A minus R-134a, in psi. Vacuum cells are in inches of mercury.

Suction side: saturated vapor (dew point) pressure

Temperature°CR-513A, psigR-134a, psigDifference, psi
-20 °F-28.90.43.7″ Hg+2.2
0 °F-17.89.56.5+3.0
20 °F-6.722.418.4+4.0
40 °F4.440.135.0+5.1
50 °F10.051.045.4+5.6
70 °F21.177.771.1+6.6
80 °F26.793.886.7+7.1
90 °F32.2111.9104.3+7.6
95 °F35.0121.7114.0+7.7
105 °F40.6143.1135.0+8.1
115 °F46.1166.9158.4+8.5
130 °F54.4207.5198.7+8.8

Liquid line: saturated liquid (bubble point) pressure

Temperature°CR-513A, psigR-134a, psigDifference, psi
-20 °F-28.90.53.7″ Hg+2.3
0 °F-17.89.66.5+3.1
20 °F-6.722.518.4+4.1
40 °F4.440.135.0+5.1
50 °F10.051.145.4+5.7
70 °F21.177.771.1+6.6
80 °F26.793.886.7+7.1
90 °F32.2111.9104.3+7.6
95 °F35.0121.7114.0+7.7
105 °F40.6143.1135.0+8.1
115 °F46.1166.9158.4+8.5
130 °F54.4207.5198.7+8.8

Same gauge reading, different saturation temperature

ReadingPressureR-513A saturationR-134a saturationError with the wrong chart
Suction gauge35 psig34.8 °F40.0 °F5.2 °F
Liquid gauge135 psig101.3 °F105.0 °F3.7 °F

Suction readings use the vapor (dew) column and liquid readings the liquid (bubble) column. The last column is how far off superheat or subcooling would be if the R-134a chart were used on R-513A, or the other way round.

R-513A and R-134a side by side

R-513AR-134a
Safety classA1 (lower toxicity, no flame propagation)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026)A1 (lower toxicity, no flame propagation)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026)
GWP (100-year)630 per US EPA (AR4, calculated for the blend)US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two.1,430 per US EPA (IPCC 2007 (AR4))US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two.
Temperature glide0.0 °F at a 40 °F dew point and 0.0 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart)None: a single-component refrigerant has one saturation temperature at each pressure.
Compressor lubricantPOE (polyolester)Arkema, 2025 Forane® Technical DigestPOE; PAG in automotive AC onlyArkema, 2025 Forane® Technical Digest
Sold as a replacement forR-134a, except in automotive ACArkema, 2025 Forane® Technical DigestR-12Arkema, 2025 Forane® Technical Digest
Typical useMedium-temp refrigeration and chillers (R-134a replacement)Medium-temp refrigeration, chillers, vehicles
Pressure dataArkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025)Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025)

Can R-513A replace R-134a?

Arkema lists R-513A as a replacement for R-134a, except in automotive AC, typically with POE oil (Arkema, 2025 Forane® Technical Digest).

A changeover follows the refrigerant maker's and the equipment maker's instructions. This page only compares the published pressure data.

Calculators and full charts

The whole job, on your phone

HVAC Charge: Superheat & PT

R-513A, R-134a and 20 more refrigerants on your phone, offline: superheat, subcooling and PT lookup. See what's inside.

Questions

Is R-513A higher or lower pressure than R-134a?

At 105 °F saturated liquid R-513A is 143.1 psig and R-134a is 135.0 psig, a difference of +8.1 psi. At 40 °F saturated vapor it is 40.1 psig against 35.0 psig (+5.1 psi).

Can I use the R-134a PT chart for R-513A?

No. At 35 psig on the suction side the two charts give 34.8 °F for R-513A and 40.0 °F for R-134a, so superheat would be off by 5.2 °F. At 135 psig on the liquid line subcooling would be off by 3.7 °F. Use the chart for the refrigerant in the system.

Which has more temperature glide, R-513A or R-134a?

R-513A: 0.0 °F at a 40 °F dew point and 0.0 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart). R-134a: none: a single-component refrigerant has one saturation temperature at each pressure..

Can R-513A replace R-134a in an existing system?

Arkema lists R-513A as a replacement for R-134a, except in automotive AC, typically with POE oil (Arkema, 2025 Forane® Technical Digest). A changeover follows the refrigerant maker's and the equipment maker's instructions; this page only compares published pressure data.

Reference only. Charging targets and procedures come from the equipment manufacturer's data plate and installation instructions, and local codes apply. Handling refrigerants requires EPA Section 608 certification in the US.