R-32 vs R-410A: pressures, glide and safety class
The published PT charts of R-32 and R-410A side by side at the same temperatures, with glide, safety class and GWP.
Quick answer: at the same temperatures R-32 runs at higher pressure than R-410A. As saturated vapor at 40 °F, R-32 is 121.0 psig against 118.8 psig (+2.2 psi). As saturated liquid at 105 °F, R-32 is 349.7 psig against 341.9 psig (+7.8 psi, about 2 % higher).
R-32 and R-410A pressure at the same temperature
Difference = R-32 minus R-410A, in psi. Vacuum cells are in inches of mercury.
Saturation pressure
| Temperature | °C | R-32, psig | R-410A, psig | Difference, psi |
|---|---|---|---|---|
| -40 °F | -40.0 | 11.0 | 10.8 | +0.2 |
| -20 °F | -28.9 | 26.8 | 26.3 | +0.5 |
| 0 °F | -17.8 | 49.3 | 48.4 | +0.9 |
| 20 °F | -6.7 | 80.0 | 78.7 | +1.3 |
| 40 °F | 4.4 | 121.0 | 118.8 | +2.2 |
| 50 °F | 10.0 | 145.9 | 143.2 | +2.7 |
| 70 °F | 21.1 | 205.8 | 201.8 | +4.0 |
| 80 °F | 26.7 | 241.5 | 236.5 | +5.0 |
| 90 °F | 32.2 | 281.3 | 275.4 | +5.9 |
| 95 °F | 35.0 | 302.9 | 296.4 | +6.5 |
| 105 °F | 40.6 | 349.7 | 341.9 | +7.8 |
| 115 °F | 46.1 | 401.4 | 392.3 | +9.1 |
| 130 °F | 54.4 | 489.5 | 477.9 | +11.6 |
Same gauge reading, different saturation temperature
| Reading | Pressure | R-32 saturation | R-410A saturation | Error with the wrong chart |
|---|---|---|---|---|
| Suction gauge | 119 psig | 39.1 °F | 40.1 °F | 0.9 °F |
| Liquid gauge | 342 psig | 103.4 °F | 105.0 °F | 1.6 °F |
Suction readings use the vapor (dew) column and liquid readings the liquid (bubble) column. The last column is how far off superheat or subcooling would be if the R-410A chart were used on R-32, or the other way round.
R-32 and R-410A side by side
| R-32 | R-410A | |
|---|---|---|
| Safety class | A2L (lower toxicity, lower flammability)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026) | A1 (lower toxicity, no flame propagation)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026) |
| GWP (100-year) | 675 per US EPA (IPCC 2007 (AR4))US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two. | 2,088 per US EPA (AR4, calculated for the blend)US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two. |
| Temperature glide | None: a single-component refrigerant has one saturation temperature at each pressure. | The source chart prints one pressure column, used for both superheat and subcooling. |
| Compressor lubricant | POE (polyolester)Arkema, 2025 Forane® Technical Digest | POE (polyolester)Arkema, 2025 Forane® Technical Digest |
| Sold as a replacement for | R-410A, in new equipmentArkema, 2025 Forane® Technical Digest | – |
| Typical use | AC, heat pumps and mini-splits | Residential and light commercial AC and heat pumps |
| Pressure data | Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025) | Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025) |
Can R-32 replace R-410A?
Arkema lists R-32 as a replacement for R-410A in new equipment (Arkema, 2025 Forane® Technical Digest). It is an A2L refrigerant, and Chemours' guide states that A2L refrigerants are for new equipment only, not for retrofits (Chemours, Opteon™ XL41 (R-454B) Pressure-Temperature Guide for A/C).
A changeover follows the refrigerant maker's and the equipment maker's instructions. This page only compares the published pressure data.
Calculators and full charts
HVAC Charge: Superheat & PT
R-32, R-410A and 20 more refrigerants on your phone, offline: superheat, subcooling and PT lookup. See what's inside.
Questions
Is R-32 higher or lower pressure than R-410A?
At 105 °F saturated liquid R-32 is 349.7 psig and R-410A is 341.9 psig, a difference of +7.8 psi. At 40 °F saturated vapor it is 121.0 psig against 118.8 psig (+2.2 psi).
Can I use the R-410A PT chart for R-32?
No. At 119 psig on the suction side the two charts give 39.1 °F for R-32 and 40.1 °F for R-410A, so superheat would be off by 0.9 °F. At 342 psig on the liquid line subcooling would be off by 1.6 °F. Use the chart for the refrigerant in the system.
Which has more temperature glide, R-32 or R-410A?
R-32: none: a single-component refrigerant has one saturation temperature at each pressure.. R-410A: the source chart prints one pressure column, used for both superheat and subcooling..
Can R-32 replace R-410A in an existing system?
Arkema lists R-32 as a replacement for R-410A in new equipment (Arkema, 2025 Forane® Technical Digest). It is an A2L refrigerant, and Chemours' guide states that A2L refrigerants are for new equipment only, not for retrofits (Chemours, Opteon™ XL41 (R-454B) Pressure-Temperature Guide for A/C). A changeover follows the refrigerant maker's and the equipment maker's instructions; this page only compares published pressure data.
Reference only. Charging targets and procedures come from the equipment manufacturer's data plate and installation instructions, and local codes apply. Handling refrigerants requires EPA Section 608 certification in the US.