R-449A vs R-404A: pressures, glide and safety class
The published PT charts of R-449A and R-404A side by side at the same temperatures, with glide, safety class and GWP.
Quick answer: at the same temperatures R-449A runs at pressures close to, but not the same as, R-404A. As saturated vapor at 40 °F, R-449A is 71.8 psig against 86.9 psig (-15.1 psi). As saturated liquid at 105 °F, R-449A is 257.8 psig against 254.2 psig (+3.6 psi, about 1 % higher).
R-449A and R-404A pressure at the same temperature
Difference = R-449A minus R-404A, in psi. Vacuum cells are in inches of mercury.
Suction side: saturated vapor (dew point) pressure
| Temperature | °C | R-449A, psig | R-404A, psig | Difference, psi |
|---|---|---|---|---|
| -40 °F | -40.0 | 0.0 | 4.9 | -4.9 |
| -20 °F | -28.9 | 9.9 | 16.8 | -6.9 |
| 0 °F | -17.8 | 24.3 | 33.7 | -9.4 |
| 20 °F | -6.7 | 44.5 | 56.6 | -12.1 |
| 40 °F | 4.4 | 71.8 | 86.9 | -15.1 |
| 50 °F | 10.0 | 88.7 | 105.3 | -16.6 |
| 70 °F | 21.1 | 129.7 | 149.3 | -19.6 |
| 80 °F | 26.7 | 154.3 | 175.4 | -21.1 |
| 90 °F | 32.2 | 182.0 | 204.5 | -22.5 |
| 95 °F | 35.0 | 197.1 | 220.2 | -23.1 |
| 105 °F | 40.6 | 229.9 | 254.2 | -24.3 |
| 115 °F | 46.1 | 266.5 | 291.8 | -25.3 |
| 130 °F | 54.4 | 329.2 | 355.7 | -26.5 |
Liquid line: saturated liquid (bubble point) pressure
| Temperature | °C | R-449A, psig | R-404A, psig | Difference, psi |
|---|---|---|---|---|
| -40 °F | -40.0 | 4.5 | 4.9 | -0.4 |
| -20 °F | -28.9 | 16.4 | 16.8 | -0.4 |
| 0 °F | -17.8 | 33.4 | 33.7 | -0.3 |
| 20 °F | -6.7 | 56.6 | 56.6 | +0.0 |
| 40 °F | 4.4 | 87.4 | 86.9 | +0.5 |
| 50 °F | 10.0 | 106.1 | 105.3 | +0.8 |
| 70 °F | 21.1 | 151.0 | 149.3 | +1.7 |
| 80 °F | 26.7 | 177.6 | 175.4 | +2.2 |
| 90 °F | 32.2 | 207.2 | 204.5 | +2.7 |
| 95 °F | 35.0 | 223.2 | 220.2 | +3.0 |
| 105 °F | 40.6 | 257.8 | 254.2 | +3.6 |
| 115 °F | 46.1 | 295.9 | 291.8 | +4.1 |
| 130 °F | 54.4 | 360.2 | 355.7 | +4.5 |
Same gauge reading, different saturation temperature
| Reading | Pressure | R-449A saturation | R-404A saturation | Error with the wrong chart |
|---|---|---|---|---|
| Suction gauge | 87 psig | 49.0 °F | 40.1 °F | 9.0 °F |
| Liquid gauge | 254 psig | 103.9 °F | 104.9 °F | 1.0 °F |
Suction readings use the vapor (dew) column and liquid readings the liquid (bubble) column. The last column is how far off superheat or subcooling would be if the R-404A chart were used on R-449A, or the other way round.
R-449A and R-404A side by side
| R-449A | R-404A | |
|---|---|---|
| Safety class | A1 (lower toxicity, no flame propagation)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Refrigerated Food Processing and Dispensing Equipment (page updated 20 March 2026) | A1 (lower toxicity, no flame propagation)ASHRAE Standard 34 class as listed by US EPA SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (page updated 19 March 2026) |
| GWP (100-year) | 1,396 per US EPA (AR4, calculated for the blend)US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two. | 3,922 per US EPA (AR4, calculated for the blend)US EPA, Technology Transitions GWP Reference Table (page updated 2 April 2026). Every GWP on this site is EPA's figure; refrigerant makers' literature can differ by a unit or two. |
| Temperature glide | 9.4 °F at a 40 °F dew point and 7.7 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart) | The source chart prints one pressure column, used for both superheat and subcooling. |
| Compressor lubricant | POE (polyolester)Arkema, 2025 Forane® Technical Digest | POE (polyolester)Arkema, 2025 Forane® Technical Digest |
| Sold as a replacement for | R-404A, R-507A, R-22 and the R-407 seriesArkema, 2025 Forane® Technical Digest | R-502Arkema, 2025 Forane® Technical Digest |
| Typical use | Low and medium-temp refrigeration (R-404A replacement) | Low and medium-temp commercial refrigeration |
| Pressure data | Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025) | Arkema Forane® Pressure Temperature Chart (PPC/SDC 05-2025) |
Can R-449A replace R-404A?
Arkema describes R-449A as designed to replace R-404A, R-507A, R-22 and the R-407 series, typically with POE oil (Arkema, 2025 Forane® Technical Digest).
A changeover follows the refrigerant maker's and the equipment maker's instructions. This page only compares the published pressure data.
Calculators and full charts
HVAC Charge: Superheat & PT
R-449A, R-404A and 20 more refrigerants on your phone, offline: superheat, subcooling and PT lookup. See what's inside.
Questions
Is R-449A higher or lower pressure than R-404A?
At 105 °F saturated liquid R-449A is 257.8 psig and R-404A is 254.2 psig, a difference of +3.6 psi. At 40 °F saturated vapor it is 71.8 psig against 86.9 psig (-15.1 psi).
Can I use the R-404A PT chart for R-449A?
No. At 87 psig on the suction side the two charts give 49.0 °F for R-449A and 40.1 °F for R-404A, so superheat would be off by 9.0 °F. At 254 psig on the liquid line subcooling would be off by 1.0 °F. Use the chart for the refrigerant in the system.
Which has more temperature glide, R-449A or R-404A?
R-449A: 9.4 °F at a 40 °F dew point and 7.7 °F at a 105 °F bubble point (dew minus bubble temperature at the same pressure, computed from this chart). R-404A: the source chart prints one pressure column, used for both superheat and subcooling..
Can R-449A replace R-404A in an existing system?
Arkema describes R-449A as designed to replace R-404A, R-507A, R-22 and the R-407 series, typically with POE oil (Arkema, 2025 Forane® Technical Digest). A changeover follows the refrigerant maker's and the equipment maker's instructions; this page only compares published pressure data.
Reference only. Charging targets and procedures come from the equipment manufacturer's data plate and installation instructions, and local codes apply. Handling refrigerants requires EPA Section 608 certification in the US.
https://zhukovskyi.space/calculators/hvac/compare/r-449a-vs-r-404a.html · checked 12 November 2026